Technical Data - Bosch FMR-5000-C Guide D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 26
FMR-5000-C
CAUTION!
If Ethernet networking is planned, the Remote Keypad must be grounded.
Address Setting and Configuration
1.
2.
3.

Technical Data

LCD Ddisplay / touch screen
Operating and display elements
Interfaces
Signal inputs
Permissable length of CAN cable for system
networking
Power supply connection
Input voltage
Maximum line restance of power supply
Maximum current consumption
Permissible operating temperature
Permissible storage temperature
Housing material and color
Dimansions (H x W x D)
Weight
Bosch Sicherheitssysteme GmbH
Assign a unique physical address to each Panel Controller and Remote Keypad by setting
the rotary switches and write it down on the label (see Figure 13, Page 15, step 1 and 2).
For configuration, set the 6-pin DIP switch (see Figure 13, Page 15, step 3).
Mark the setting on the provided label (step 4).
LCD display with 320 x 240 pixels, touch screen with
127,5 mm x 170 mm active surface
22 buttons, 1 key switch, 11 LEDs, 1 Reboot button
CAN1, CAN2, ETH1, ETH2, USB, RS232
IN1/IN2
L
max
DC1 (power supply), DC2 (redundant power supply)
12 V DC to 30 V DC, from FPA-5000 or FPP-5000
18 Ω
-
-
-5 °C to +50 °C
-20 °C to +70 °C
ABS plastic, light gray (similar RAL 7035)
280 mm x 340 mm x 87 mm
Approx. 3 kg
= 1000 m, depending on configuration, cable type and topology
Standby operation: 140 mA at 24 V DC
During an alarm: 230 mA at 24 V DC
en
23
F.01U.258.926 | 3.0 | 2012.09