Unwanted Sensor Activations (LED flashes):
Possible causes
1. The ultrasonic sensitivity may be too high causing detection outside of desired coverage area.
2. Sensor located too close to HVAC or VAV vents with heavy air flow.
3. If LED is flashing rapidly (~10Hz), an overload condition exists. When this is corrected, the sensor will return to normal operation.
Possible solutions
1. Reduce the ultrasonic sensitivity (counterclockwise) as needed (see "Sensor Adjustment").
2. Relocate the sensor.
3. Check the blue wire connection. If necessary, replace the power pack.
Catalog#
UT-305-1
Ultrasonic Occupancy Sensor, up to 300 sq ft coverage, Low Voltage with Manual On Feature
UT-305-2
Ultrasonic Occupancy Sensor, up to 1000 sq ft coverage, Low Voltage with Manual On Feature
UT-305-3
Ultrasonic Occupancy Sensor, up to 2000 sq ft coverage, Low Voltage with Manual On Feature
BZ-50
Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent
BZ-150
Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent, with Hold-On and Hold-Off capability
BZ-200
Power Pack: 120/277VAC, 50/60 Hz, 20A Ballast/ELV/MLV/Incandescent/LED, 16A, E-Ballast/CFL/Plug Load
BZ-250
Power Pack: 120/277VAC, 50/60 Hz, 20A, Ballast/ELV/MLV/Incandescent/LED, 16A E-Ballast/CFL/Plug Load,
with Hold-On/Hold-Off capability
BZ-250-347
Power Pack: 120/347VAC, 50/60 Hz, 16A Ballast/ELV/MLV/Incandescent/LED/ E-Ballast/CFL, 15A Plug Load,
with Hold-On/Hold-Off capability
Sensors are White. BZ series power packs supply power for up to 5 UT-305 sensors.