Pulsar M
5.3
Maintenance on a UPS Equipped With the HotSwap MBP Module
5 — 4
The HotSwap MBP module makes possible to
service or even replace the UPS without affecting
the connected loads (HotSwap function).
Maintenance:
1. Set switch (53) to the Bypass position. The
2. Stop the UPS by pressing the ON/OFF button
Return to normal operation:
1. Check that the UPS is correctly connected
2. Start the UPS by pressing the ON/OFF button
3. Set switch (53) to the Normal position. The
Maintenance
E E N N G G L L I I S S H H
red LED (52) on the HotSwap MBP module
goes ON, indicating that the load is supplied
directly with AC power.
(27) on the UPS control panel. LED (51)
"UPS ON - OK to switch" goes OFF, the UPS
can now be disconnected and replaced.
to the HotSwap MBP module.
(27) on the UPS control panel. LED (51)
"UPS ON - OK to switch" on the HotSwap
MBP module goes ON (otherwise, there is a
connection error between the HotSwap MBP
module and the UPS).
red LED (52) on the HotSwap MBP module
goes OFF.
86-86710-00 A01