E N G L I S H
2.7
Connection with a HotSwap MBP Module (optional)
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads
(HotSwap function).
Evolution 2500 / 3000
HotSwap MBP
Evolution S 1750 / 2000
HotSwap MBP
49
86-81710-00 A01
All manuals and user guides at all-guides.com
54
55
55
53
54
Installation
Installation and User Manual
1. Connect the input socket (56) on the HotSwap
MBP module to the AC-power source using the
cable (31) supplied.
2. Connect the UPS input socket (10) to the "UPS
Input" (55) on the HotSwap MBP module.
3. Evolution S 2500 / S 3000: Connect the UPS
outlet (7) to the "UPS Output" (54) on the
HotSwap MBP module.
Evolution S 1250 / S 1750 / 2000: Connect one
of the UPS outlets (9) to the "UPS Output" (54) on
the HotSwap MBP module.
4. Connect the equipment to the outlets (49) on the
HotSwap MBP module.
These outlets differ, depending on the version of the
HotSwap MBP module.
Caution: Do not use UPS outlets (8) and (9) to
supply equipment because use of switch (53) on
the HotSwap MBP module would cut supply to the
equipment.
2 — 5