E E N N G G L L I I S S H H
HotSwap MBP module operation
UPS start-up with the HotSwap MBP module
1.
Check that the UPS is correctly connected to the HotSwap MBP module.
2.
Set switch (53) to the Normal position.
3.
Start the UPS by pressing the ON/OFF button (27) on the UPS control panel.
The load is supplied by the UPS.
LED (51) "UPS ON - OK to switch" on the HotSwap MBP module goes ON.
HotSwap MBP module test
1.
Set switch (53) to the Bypass position and check that the load is still supplied.
2.
Set switch (53) back to the Normal position.
2.7
UPS Connection Without a FlexPDU or HotSwap MBP Module
Check that the indications on the name plate located on the back of the UPS correspond to the AC power source and the
true electrical consumption of the total load.
i
i
Note: The UPS charges the battery as soon as it is connected to the AC power source, even if button (27) is not pressed.
Once the UPS is connected to the AC power source, eight hours of charging are required before the battery can supply
the rated backup time
86-86710-00 A01
Installation and User Manual
The HotSwap MBP module has a rotary
switch (53) with two positions:
Normal – the load is supplied by the UPS,
Bypass – the load is supplied directly by the
1. Connect the input cord (31) (120V 30A / or
20A on Pulsar M 2200) to the AC power
source.
2. Connect the loads to the UPS.
It is preferable to connect the priority loads
to the four outlets marked (9) and the non-
priority loads to the two outlets marked (8)
that can be programmed. Connect any high-
power devices to the 20A (or 30A on Pulsar
M 3000) outlet (7) as shown at left for Pulsar
M 2200.
To program shutdown of outlets (8) during
operation on battery power and thus optimise
the available backup time, the MGE Office
Protection Systems communications software
is required.
Installation
LED (51) is ON.
AC power source. LED (52) is ON.
2 — 5