Electrical Installation - Master DARK 15 Manuel D'utilisation Et De Maintenance

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Electrical installation

Warnings
The installation should always be carried out by a qualified
electrician or a competent person in accordance with the current
electrical standards:
HD 384 CENELEC for Mainland Europe, IEC 60446 and BS 7671
for the United Kingdom, IEC 60445(2010) & ET101:2008 for Ireland
and IEC 60364-7 1988 Internationally.
The energy supply to the heater must always be properly earthed.
The appliance must be connected to energy supply line by means
of the provided H05SS-F silicone cable.
An overvoltage category III Combined Circuit breaker and Residual
Current Device (RCD) with rated earth leakage operation not
exceeding 30mA must be fitted upstream on the supply line. The
circuit breaker must have a contact opening distance of at least 3
mm.
The product is in class I and IP55, wich is the protection rate for
the units to be used even outdoor. For keeping the protection rate
of the appliance, the connection of the appliance with the power
supply must be done by means of a minimum IP55 system, as per
the standards HD 384 CENELEC for Europe, or international IEC
.
60364-7 1988
Before connecting the appliance make sure that
the voltage is the same as indicated on the device
and the line supply is corresponding to the effective
rules.
34

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Dark 18Dark 24Dark 32

Table des Matières