INSTALLATION MANUAL
DGLPTWLC
Indoor/Outdoor Proximity Card readers - Wiegand

1] GENERAL INFORMATION

Wiegand 26, 30 and 44 bits.
Audible and visual feedback
Direct connection to the controller
through the door controller
(INTBUSW).
Flush mount.
Polycarbonate.
Sealed (resin moulded).
Connection by 4 pair 6/10th cable
Input voltage : 12 V DC.
Consumption : 100 mA.
Conforms to European directive R&TTE 99/5/CE and
according to the harmonised standards : ETS 301 489
and ETS 300-330-1-Ed 2001. Conforms to CEM applied
directives : EN 50133, EN 50130-4.
2] NOTES AND RECOMMENDATIONS
Installation recommendations
To make the installation secure, remember to:
- install the varistor on the locking system, in paral-
lel on the supply circuit.
- place a 120 ohms resistance, between A and B, on
the last door controller of the RS485 BUS.
Recommended cable
4 pair 6/10th cable.

3] MOUNTING KIT

DGLPTWLC
cdvi.com
2
cdvigroup.com
DGLPTWLC
Screw
reader
1
1
WEEE & RoHS
CE Certification
R&TTE Certification
Wiring reminder
Warning: do not route your wires close to cables
carrying a high current (e.g. : 230 V AC).
Recommended power supplies
Two power supplies are suitable : ARD12 or BS60.
These products must be powered in 12Vdc and the
power supply should be certified EN60950-1:2006/
A11:2009 standards and should be designed
to be a low power supply source.
electronic
box
1
IP64
-25°C to +55°C
jumper
2
1