INSTALLATION MANUAL
CA-A482-P
Destination reporting module
WIRING THE DRM AND CA-A480-A
The CA-A480-A and DRM can only be wired using the fail-safe connection method (Refer to the CA-A480-A
Elevator Controller Reference & Installation Manual). Wire the DRM and CA-A480-A as shown below.
To connect the DRM and CA-A480-A:
1. Connect the "COM" terminal of the selected fl oor control relay of the CA-A480-A to the desired fl oor button
in the elevator car.
2. Connect the "NC" terminal of the selected fl oor control relay of the CA-A480-A to the button input
of the elevator control system.
3. Connect the "COM" terminal of the DRM to the "-" or ground of the elevator.
4. Connect the selected "IN" (Floor Selection Input) terminal of the DRM to the wire connecting
the CA-A480-A's "COM" terminal and the fl oor button in the elevator car.
Elevator Control System
Floor Button's "common" terminal
Floor Button's input terminal
Loop terminal added
by installer
Elevator car
floor button
To "COM" input
terminal of desired
Floor Control Relay
To "NC" input
terminal of desired
Elevator (-) or
Floor Control Relay
GND Common
DESTINATION REPORTING MODULE (CA-A482-P) SPECIFICATIONS:
Input Voltage:
Connection Method:
Input Current:
Input Response Time:
Floor Select Inputs:
Temperature:
Galvanic Isolation:
Operating Humidity:
Select Activation LED:
Removable Terminals:
Min. DC Input Activation:
Multiple Select Avoidance: Yes (CT-V900-A Control)
Max. DC Input Activation:
CA-A480-A elevator Controller
E-BUS
A+
IN1
CM1
IN2
CM2
IN3
CM3
IN4
CM4
16-floor DRM
COM2
(CA-A482-P)
IN5
CM5
mounted on CA-A480-A
IN6
CM6
ÌN7
CM7
IN8
CM8
+5 VDC
14-way Flat Cable to CA-A480-A
28mA (maximum 108mA)
700 mS
16 Operating
15°C to 55°C (59°F to 131°F)
< 2500 Vrms
10% to 95%
Yes (16 LEDs)
Yes
15 VDC
165 VDC
+
AC
AC
BAT+
IN 1
IN 9
IN 2
IN 10
BAT-
IN 3
IN 11
IN 4
IN 12
+12V
IN 5
IN 13
IN 6
IN 14
+12V
IN 7
IN 15
GND
IN 8
IN 16
GND
FC
FC
NC16
NO16
COM16
NC15
NO15
COM15
NC14
ADDRESS 1
NO14
ADDRESS 2
ADDRESS 4
ADDRESS 8
COM14
RLY COMMS
RLY OFF/ON
NC13
DRM ENABLED
PWR OFF/ON
NO13
RL10
RL11
RL12
COM13
www.cdvigroup.com
Disconnect AC
and
battery
power before
mounting the
DRM to the
CA-A480-A.
www.cdvi.com