4. Temperature sensor
Installation
A
B
1
Fig. 2
1.
Place the O-ring from the attached coupling set (type A or B) on the mounting pin.
2.
Insert the O-ring with the mounting pin into the sensor hole of the ball valve (turn the mounting pin).
3.
Position the O-ring in its final position using the other end of the mounting pin.
4.
Fastening screws
• Type A (plastic) - plug the fastening screw onto the temperature sensor.
• Type B (brass) - insert the temperature sensor in the fastening screw and place the sensor in the
mounting pin. Press in the dowel pin completely and remove the mounting pin.
5.
Insert the temperature sensor with the securing fitting in the ball valve and manually tighten (2-3 Nm).
4.2 Installation in a pocket
For new installations, temperature sensors for nominal sizes DN25 or smaller should only be installed directly
immersed. This ensures higher measuring accuracy.
3
2
5
4
A
B
A
B
33