Short-Circuit Back-Up Fuse; Undervoltage Release; Safety Instructions - Cooper Crouse-Hinds CEAG GHG 635 Mode D'emploi

Disjoncteurs moteur jusqu'à 16 a
Masquer les pouces Voir aussi pour CEAG GHG 635:
Table des Matières

Publicité

Manual motor starter GHG 635
Fig. 1
Wiring diagram
I>
I>
I>
L
N
PE
Dimensions in mm
10
10
10
10
10
Cooper Crouse-Hinds GmbH
Manual motor starters up to 16 A, GHG 635
1.4
Manual motor starters GHG 635
Marking acc. to 94/9/EC:
EC type examination certificate:
Rated voltage:
Rated current 3 pole:
Rated current 2 pole:
Short circuit back-up fuse:
AC 3 switching capacity 3 pole:
AC 3 switching capacity 2 pole:
Thermal tripping characteristic:
Tripping time:
Perm temperature
moveable connecting cable
non moveable connecting cable
Other temperatures possible for special versions.
Perm.storage temperature in original packing:
Protection category acc. to EN60529:
Insulation class acc. to EN/IEC 61140:
Connection:
2 x trumpet shaped cable entry
Minimum bending radius of connecting cable:
2 x 5 x 1,5 mm²
2 x 5 x 2,5 mm²
Test torques:
at panel mounting with spring washer
Clamping screws of the trumpet strain relief
Weight:
Standard design
1.5
Undervoltage release (only 3 pole version)
Rated voltage:
Other versions possible.
Drop value:
Starting value:
Short circuit back-up fuse:
2
carried out by electrical suitably trained in
hazardous area with knowledge of
increased safty explosion protection
EN/IEC 60079-14.
PE
L
N
The requirements of the EN 61241-0 and -1
regarding excessive dust deposits and
temperature to be considered from the
user.
The manual motor starters are not
suitable for zone 0 and 20 hazardous
areas.
The temperature class and type of
protection stated on the apparatus shall
be observed.
Modifications or changes to the manual
motor starters are not permitted.
They shall be used for their intended
purpose and shall be in a perfect and
clean state.
Prior to being put into operation, the
(bis 12,5 A)
(bis 16,0 A)

Safety instructions

The operations must be
II 2 G Ex d II C T6
II 2 D Ex tD A21 IP66 T80°C
PTB 05 ATEX 1020
690 V, 50/60 Hz / 440 V DC
0.1 A to 16.0 A
4.0 A to
6.3 A
see point 1.4 and 1.5, page 4
690 V / 16 A
230 V / 6.3 A
T II
see diagram 1, S.3
-20° C to +40° C (standard version)
-5° C to +40° C
-20° C to +40° C
-40° C to +80° C
IP 66 (standard version)
I - device fulfil this requirement
(standard)
2 x 5 x 1,0 mm²
(up to 10,0 A)
2 x 5 x 1,5 mm²
(up to 12,5 A)
2 x 5 x 2,5 mm²
(up to 16,0 A)
min. 75 mm
min. 93 mm
2,0 Nm
1,5 Nm
approx. 2.0 kg
400 V 50/60 Hz (standard version)
35....70 % von U c
>85 % von U c
not necessary
manual motor starters shall be checked in
accordance with the instructions as per
section 6.
Warning:
The national safety rules and regulations
for the prevention of accidents, as well as
the safety instructions included in these
operating instructions, that, like this text,
are set in italics, shall be observed!
3
Conformity with standards
The manual motor starters are conform to the
standards specified in the EC-Declaration of
conformity, enclosed separately.
It has been designed, manufactured and
tested according to the state of the art and to
DIN EN ISO 9001.
94/9 EC: Equipment and protective systems
intended for use in potentially explosive
atmospheres.
The manual motor starters fulfil further
requirements such as those of the EC
directive on electromagnetic compatibility
(2004/108/EEC)