Manual Motor Starters; Technical Data; Auxiliary Contact; Undervoltage Release - Cooper Crouse-Hinds GHG 635 Série Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Manual motor starter GHG 635
Diagram 1
Multiple of setting current
1 =
thermal tripping
2 =
electromagnetic tripping
Wiring diagram
8 8 8 8 8
Cooper Crouse-Hinds GmbH
Manual motor starters up to 25A, GHG 635
1

Technical data

1.1
Manual motor starters GHG 635
Marking acc. to 94/9/EC:
*
Temperature class, see 1.6, page 9
EC type examination certificate:
Rated voltage:
Rated current:
Short circuit back-up fuse:
AC 3 switching capacity:
Thermal tripping characteristic:
Tripping time:
Perm.storage temperature in original packing:
Other temperatures possible for special versions.
Perm.storage temperature in original packing:
Degree of protection acc. to EN/IEC 60529:
Insulation class acc. to EN/IEC 61140:
Cable entries:
0.1A - 6.3A
6.3A - 25.0A
with auxiliary contact / undervoltage release
Supply terminals:
Test torques:
Cap nut of the cable entry M 25
Cap nut of the cable entry M 32
Cover screws
Terminals (main contacts)
Terminals (auxiliary contacts)
Terminals (under voltage contacts)
Weight:
Standard design
with auxiliary contact / undervoltage release
1.2

Auxiliary contact

Rated voltage:
Rated current:
AC 15 switching capacity:
DC 13 switching capacity:
Perm. short circuit back-up fuse:
Terminals:
1.3

Undervoltage release

Rated voltage:
Drop value:
Starting value:
Short circuit back-up fuse:
Terminals:
Dimensions in mm
X = fixing dimensions
II 2 G Ex e d II C T6 / T5*
II 2 D Ex tD A21 IP66 80° C
PTB 99 ATEX 1162
690 V, 50/60 Hz / 440 V DC
up to 25 A
see point 1.4 and 1.5, page 4
690 V / 25 A
T II
see diagram 1, page 3, also point 1.7, page 5
-20° C up to +40° C (standard version)
-50° C to +80° C
IP 66 (standard version)
I - device fulfil this requirement
II - with metal flange
(standard version)
2 x M25 for cable
Ø
8 - 17 mm
2 x M32 for cable
Ø 12 - 21 mm
1 x M25 in addition
2 x 0.75 - 4.0 mm² or
1 x 10 mm²
3.5 Nm
5.0 Nm
2.5 Nm
3.5 Nm
2.5 Nm
2.5 Nm
approx. 2.45 kg
approx. 2.55 kg
up to 400V AC
up to 2 A
230 V / 2 A
400 V / 0.50 A
60 V / 2 A
230 V / 0.25 A
max. 10 A gL
2 x 0.75 - 2.5 mm²
110 V, 230 V, 400 V, 500 V 50/60 Hz
35....75 % E c
>85 % E c
not necessary
2 x 0.75 - 2.5 mm²

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ceag ghg 635

Table des Matières