21. Reinstall the panelboard cover(s).
22. Test the SurgePOD PRO installation by energizing the panelboard
and placing the circuit breaker or fusible switch (requires fuses
to be installed) in the ON position. Verify the LED status indicator
is ON and Green. If LED is not ON or Green, see easyID™ LED
Status Indicators on page 4 for possible causes and remedy.
Dimensions - in
3-3/8"
2-1/16"
4-1/8"
4
Eaton.com/bussmannseries
White
1-1/16" Dia.
1-11/16"
1-11/16"
2-1/16"
3-3/16"
4-1/16"
7/8"
Type 1 surge protective device
Specifications
Specification
Catalog number
Nominal system voltage
Max. Continuous Operating
Voltage (AC) (MCOV) (VC)
Short-Circuit Current Rating
(SCCR)
Nom. I
Discharge
n
current (8x20µs)
Max. I
max
Response time (ns) t
A
Voltage frequency
Conductor length/guage
Enclosure/flammability ratings
Degree of protection
(installed state)
Install location
Required circuit location
Standard
Agency information
Warranty
Operating temperature range
Maximum operating altitude
*
SPP40SP2240PN is the SurgePOD PRO Type 1 SPD part number that is
contained inside the retail package number RB-SPP-240PN.
**
NEMA 4X rating requires installation with appropriate customer supplied
gasket between the unit and the panelboard wall.
*** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details
at www.cooperbussmann.com/Surge.
easyID™ LED status indicator
The easyID LED status indicator will illuminate when the unit is
properly installed and the system is energized.
The following LED colors/status indicate:
GREEN LED = Good
The circuit is energized and protected.
RED LED = Bad
The circuit is energized and unprotected.
The unit needs replacing.
LED is Out / Unlit:
The circuit is most likely deenergized.
•
The 2-pole common trip circuit breaker or
•
fused switch used for installation is turned
OFF .
The 2-pole common trip circuit breaker or fused switch used for
•
installation has opened.
The unit's leads are disconnected.
•
The unit is damaged.
•
Authorized personnel should follow all prescribed lockout/tagout
and safety procedures in troubleshooting the cause for the above
conditions. Opening the SurgePOD PRO enclosure will void warranty
and UL Listing.
SurgePOD™ PRO
Values
SPP40SP2240PN*
240V
150V L-N
300V L-L
200kA
10kA
40kA
<25 ns
50/60Hz
18 Inches of stranded 10AWG copper
NEMA 4X** - UL 94-5VA
IP20 (finger-safe)
Indoor/outdoor
Lineside or loadside of service
entrance overcurrent protective device
UL 1449 4th Edition Type 1 Listed SPD
cULus, RoHS compliant
2 Years***
-40°C to +65°C
12,000 feet