12. Specifications
PKFY Series
Model
Power source
Capacity
Dimension
Net weight
Fan Airflow rate
(Low-Middle2-Middle1-High)
Noise level
(Low-Middle2-Middle1-High)
PMFY Series
Model
Power source
Capacity
Dimension (Grille)
Net weight (Grille)
Fan Airflow rate
(Low-Middle2-Middle1-High)
Noise level
(Low-Middle2-Middle1-High)
1. Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Coolong : Indoor 27°C DB, 81°F DB/19°C WB, 67°F WB, Outdoor 35°C DB, 95°F DB
Heating : Indoor 20°C DB, 68°F DB, Outdoor 7°C DB, 45°F DB/ 6°C WB, 43°F WB
Range of application
The range of working temperatures for both the indoor and outdoor units of the series Y is as below.
Caution:
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
Mode
Indoor unit
Cooling
15°C - 24°C, 59˚F - 75˚F WB
Heating
15°C - 27°C, 59˚F - 81˚F DB
Note: As an applicable humidity standard for both indoors and outdoors, we recommend use within a range of 30 - 80% relative humidity.
Warning:
If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since there may be a refrigerant
leak. Be sure to ask the service representative whether there is refrigerant leakage or not when repairs are carried out.
The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak, however, if refrigerant gas leaks indoors, and comes
into contact with the fire of a fan heater, space heater, stove, etc., harmful substances will be generated.
PKFY-P06NBMU-E2
Cooling <BTU/h>
6,000
Heating <BTU/h>
6,700
H
<inch>
W
<inch>
32-1/8
D
<inch>
8-7/8
<Ibs>
22
DRY
<CFM>
170-180-200-210
WET
<CFM>
160-170-180-190
<dB(A)>
32-33-35-36
PMFY-P06NBMU-E
Cooling <BTU/h>
6,000
Heating <BTU/h>
6,700
H
<inch>
W
<inch>
D
<inch>
<Ibs>
DRY
<CFM>
230-250-280-300
WET
<CFM>
200-220-250-270
<dB(A)>
27-30-33-35
PUHY
–5°C - 46°C, 23˚F - 115˚F DB
–20°C - 15.5°C, –4˚F - 60˚F WB
PKFY-P08NHMU-E2
PKFY-P12NHMU-E2
Single 208/230V 60Hz
8,000
12,000
9,000
13,500
11-5/8
320-370-405
290-335-365
34-39-43
PMFY-P08NBMU-E
PMFY-P12NBMU-E
Single 208/230V 60Hz
8,000
9,000
9-1/16 (1-3/16)
33-5/8 (39-3/8)
1/-9/16 (18-1/2)
31 (7)
250-280-300-320
220-250-270-290
32-34-36-37
Outdoor unit
PURY
–5°C - 46°C, 23˚F - 115˚F DB
–20°C - 15.5°C, –4˚F - 60˚F WB
PKFY-P15NHMU-E2
PKFY-P18NHMU-E2
15,000
18,000
17,000
20,000
35-3/8
9-13/16
29
320-370-425
290-335-380
36-41-45
PMFY-P15NBMU-E
12,000
15,000
13,500
17,000
270-300-340-370
240-270-310-340
33-35-37-39
PUMY
–5°C - 46°C, 23˚F - 115˚F DB
–18°C - 15.5°C, 0˚F - 60˚F WB
19