G
Modbus – Telegram
Function 04 Read Input Register
Register
3x0001
3x0002
3x0003
Function 05 Write Single Coil
Register
0x0001
Function 08 Diagnostics
The following sub function codes are supported:
Sub Function
Parameter
Code
00
Echo of transmission data
(Loopback)
01
Restart Modbus
(Reset listen-only mode)
04
Activation listen-only mode
10
Delete counter
11
Counter bus telegrams
12
Counter communication errors
(Parity, CRC, frame errors, etc.)
13
Counter exception telegrams
14
Counter slave telegrams
15
Counter telegrams without answer
Function 17 Report Slave ID
Composition of answer telegram
Byte No.
Parameter
00
Number of bytes
01
Slave ID (device type)
02
Slave ID (device class)
03
Status
04
Version number (release)
05
Version number (version)
06
Version number (index)
Parameter
Differential
Without filtering
pressure
Differential
Filtering 1 second
pressure
Differential
Filtering 10 seconds
pressure
Parameter
AutoZero
Data Type
Signed 16 Bit
– 1000 ... + 1000
– 5000 ... + 5000
Signed 16 Bit
– 1000 ... + 1000
– 5000 ... + 5000
Signed 16 Bit
– 1000 ... + 1000
– 5000 ... + 5000
Data Type
Bit 0
Data Type
Answer
Echo data
Echo telegram
No answer
Echo telegram
Unsigned 16 Bit
All valid bus telegrams
Unsigned 16 Bit
Faulty bus telegrams
Unsigned 16 Bit
Error counter
Unsigned 16 Bit
Slave telegrams
Unsigned 16 Bit
Broadcast messages (address 0)
Data Type
Answer
Unsigned 8 Bit
6
Unsigned 8 Bit
6 = PREMASGARD
7 = PREMASGARD
30 = PREMASGARD
Unsigned 8 Bit
Unsigned 8 Bit
255 = RUN, 0 = STOP
Unsigned 8 Bit
1...9
Unsigned 8 Bit
1...99
Unsigned 8 Bit
1
14
Value
Range
– 1000 ... + 1000 Pa
– 5000 ... + 5000 Pa
– 1000 ... + 1000 Pa
– 5000 ... + 5000 Pa
– 1000 ... + 1000 Pa
– 5000 ... + 5000 Pa
Value
Range
0 / 1
ON - OFF
®
1214 (3 % )
®
1214 (1,5 %)
®
/ PREMASREG
®