Devices which operate with >35 Volt have to be
connected by a specialist.
Before putting the device into operation it should be
checked that there is no current leakage on the housing.
In case that measurements with the opened housing are
necessary, an isolating-transformer has to be integrated
for saftey reasons. Alternatively the voltage can be
supplied by an appropriate power supply which complies
with the safety regulations. All wiring work has to be done
in a voltage free state only.
Operating conditions
Operate the STD32 only with a supply voltage between 5-
32V and have in mind the polarity! (see picture1) Use a
stabilized power supply with minimum 1A output current.
If you use a mains adapter for power supply it has to be
conform with the VDE regulations.
Devices with an operating voltage >35 Volt have to be
installed by a specialist observing the VDE regulations.
Loads connected to the device are not allowed to exceed
1000W per relay.
The maximum voltage is 250V AC (alternating current)
The maximum switching power per relay is 6A
(depending on the width of the PCB tracks)
No special operation position of the device has to be
observed.
When installing the device make sure that the supply
cable has a sufficient diameter
During operation the temperature has to be between -20°
and 55° Celsius.
26