LUNA d MB
Register name Reg. no. Function
40039
38
40040
39
40041
40
40042
41
40043
42
40044
43
40045
44
40046
45
40047
46
40048
47
40049
48
40050
49
40051
50
40052
51
40053
52
22
Swegon se réserve le droit de modifier les caractéristiques de ses produits.
Description
Period time for A2
The ModBus value changes the selected period time for
at pulse output
the A2 output pulse. 5-995 = 0,5-99,5 minutes.
Runtime for in-
The ModBus value changes the selected total runtime
crease/ de- crease
for increase/decrease actuator in even 2-second inter-
actuator
vals
Valve exercise on
The ModBus value changes the selected day interval for
output D1
valve exercise on output D1. 0=Exercise off.
Valve exercise on
The ModBus value changes the selected day interval for
output D2
valve exercise on output D2. 0=Exercise off.
Valve exercise on
The ModBus value changes the selected day interval for
output A1
valve exercise on output A1. 0=Exercise off.
Valve exercise on
The ModBus value changes the selected day interval for
output A2
valve exercise on output A2. 0=Exercise off.
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Occupancy, on
Occupancy, on delay in minutes. Default = 0
delay
Occupancy, off
Occupancy, off delay in minutes. Default = 60
delay
Min
Max
5
99
20
510
0
30
0
30
0
30
0
30
0
255
0
255
03/05/2021
Unit
min
sec.
days
days
days
days
min
min