LUNA d MB
6.6.4 Zone 4x
Registre 16 bits (lecture/écriture)
Commande 04 (Lecture registre de retenue) pour lecture, commande 06 (Préréglage registre unique) ou commande 16 (Préréglage
registres multiples) pour écriture.
Register name Reg. no. Function
40001
0
40002
1
40003
2
40004
3
40005
4
40006
5
40007
6
40008
7
40009
8
40010
9
40011
10
40012
11
40013
12
40014
13
40015
14
40016
15
20
Swegon se réserve le droit de modifier les caractéristiques de ses produits.
Description
Applies to the controlling room temperature. Value
Force meas- ured
0-318 = 0-31,8°C. Force off: write FFFFH. Reading shows
room temperature
FFFFH when force is off. *)
The ModBus value replaces the temperature for the
Force desired
current operation mode. Value 20-300 = 2,0 - 30,0°C
temperature
in stages of 0,5°. Force off: write FFFFH. Reading shows
FFFFH. *)
The values 1-3 from ModBus, activates the DAY (1),
Force operation
NIGHT (2), or SAVE (3) operation mode with lower prio-
mode
rity than the timer, occupancy and external contact.
Force off: write FFFFH. Reading shows FFFFH. *)
The ModBus value replaces the heating set point in
Force heating
the controller to the output logic. Forcing of cooling
outputs
outputs has to be off. Force off: write FFFFH. Reading
shows FFFFH when force is off. *)
The ModBus value replaces the cooling set point in
Force cooling
the controller to the output logic. Forcing of heating
outputs
outputs has to be off. Force off: write FFFFH. Reading
shows FFFFH when force is off. *)
The ModBus value replaces the calculated effect value
Force power to
of the controller to output D1. Force off: write FFFFH
output D1
Reading shows FFFFH when force is off. *)
The ModBus value replaces the calculated effect value
Force power to
of the controller to output D2. Force off: write FFFFH
output D2
Reading shows FFFFH when force is off. *)
The ModBus value replaces the calculated effect value
Force power to
of the controller to output A1. Force off: write FFFFH
output A1
Reading shows FFFFH when force is off. *)
The ModBus value replaces the calculated effect value
Force power to
of the controller to output A2. Force off: write FFFFH
output A2
Reading shows FFFFH when force is off. *)
Set room tem-
The ModBus value changes the selected room tempera-
perature for DAY
ture for the DAY operation mode in the room controller.
mode
Value 20-300 = 2,0 - 30,0°C in 1/2°-stages.
Set room tempe-
The ModBus value changes the selected room tem-
rature for NIGHT
perature for the NIGHT operation mode in the room
mode
controller. Value 20-300 = 2,0 - 30,0°C in 1/2°-stages.
Set room tempe-
The ModBus value changes the selected room tempera-
rature for SAVE
ture for the SAVE operation mode in the room control-
mode
ler. Value 20-300 = 2,0 - 30,0°C in 1/2°-stages.
The ModBus value changes the selected minimum
Min. adjustable
room temperature for the DAY operation mode in
room tempera-
the room controller. Value 20-300 = 2,0 - 30,0°C in
ture for DAY mode
1/2°-stages.
The ModBus value changes the selected maximum
Max. adjustable
room temperature for the DAY operation mode in
room tempera-
the room controller. Value 20-300 = 2,0 - 30,0°C in
ture for DAY mode
1/2°-stages.
Room tem-
The ModBus value changes the selected calibration
perature sensor
value for the room units built-in sensor. Value -99 - +99
calibration
= -9,9° - +9,9°K.
External room
The ModBus value changes the selected calibration
temperature sen-
value for the exter- nal sensor. Value -99 - +99 = -9,9°
sor calibra- tion
- +9,9°K.
Min
Max
0
318
20
300
0
3
0
100
0
100
0
100
0
100
0
100
0
100
20
300
20
300
20
300
20
300
20
300
-99
99
-99
99
03/05/2021
Units
°C
°C
%
%
%
%
%
%
°C
°C
°C
°C
°C
°K
°K