Guide d'installation / Installation guide
IMEON 48V50Ah IMEON 51V100Ah
3.
Troubleshooting
Alarm description
The battery is equipped in a buzzer, which will trigger when the battery voltage is below 42V or when a cell voltage is
below 2800mV.
The alarm indicator (ALM) on front plate indicates below situations:
Status
During
charge
During
discharge
General control
1
IMBATLV_installation_guide_v.A.10
Alarm category
Cell / Total
overvoltage
Overcurrent
High temperature
Overcurrent
High temperature
Total
undervoltage
Under-voltage of
the cells
Description
Analysis
Battery is not
Check wiring.
recognized by
inverter.
Alarm
Operation
indication
Red
Stop the charge.
Red
Stop the charge.
Red
Stop the charge.
Red
Stop the discharge.
Red
Stop the discharge.
Red
Start the charge.
Red
Start the charge.
Solution
Battery : Check wiring
(communication
power)
and
setting for master and
slave batteries.
Inverter :
Check
correct
battery
configured.
and
DIP
if
is
22/ 22
EN
FR