CAUTION: Do not dispose of batteries in a fire. The batteries may explode. Dispose of
used batteries according to the instructions.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes.
It may be toxic.
CAUTION – A battery can present a risk of electrical shock and high short circuit cur-
rent. The following precautions should be observed when working on batteries:
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if battery is inadvertently grounded. If inadvertently grounded, remove
source from ground. Contact with any part of a grounded battery can result in elec-
trical shock. The likelihood of such shock can be reduced if such grounds are re-
moved during installation and maintenance.
• Failed batteries can reach temperatures that exceed the burn thresholds for touch-
able surfaces.
Product safety
• The UPS connection instructions and operation described in the manual must be fol-
lowed in the indicated order.
• UPS enclosure IP rating IP20.
• CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with
branch circuit overcurrent protection for:
• 20A rating, for Tower 3ks models, trip curve C .
• The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible.
• for PERMANENTLY CONNECTED EQUIPMENT, a readily accessible disconnect device shall
be incorporated external to the equipment.
• for PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and
shall be easily accessible.
• Check that the indications on the rating plate correspond to your AC powered system and
to the actual electrical consumption of all the equipment to be connected to the system.
• Never install the system near liquids or in an excessively damp environment.
• Never let a foreign body penetrate inside the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The admissible storage temperature range is -25°C to +55°C without batteries, 0°C to
+40°C with batteries, suggest to storage the battery below 25°C.
• This UPS can be used in TN/IT/TT power system.