Labels are attached to the air conditioning AR-053 for marking purposes. The specific
marking label depends on the applicable model of the air conditioning system and will be
created according to the unit assessment certificate. All necessary warnings are marked.
E
II 3 G Ex ec h ic mc IIB+H2 T3 Gc
Type: AR-053/260
Cert. ARTIDOR 24ATEX9999
TF & Serial No.: AS249999
Artidor Explosion Safety B.V., Emopad 38, 5663 PB Geldrop
The Netherlands, +31 (0)40 7873911, https://artidor.com
Example of a rooftop air conditioning unit label
7.
Installation instructions
General
•
Installation of explosion-safe equipment such as this product must be carried out by
personnel specially trained and qualified to do this, following the relevant requirements
of the installation standard EN 60079-14.
•
For the installation and use of this product the relevant safety regulations and also the
generally recognized latest state of the technology apply. Also follow the national
regulations and legal requirements relating to electrical connections to the electricity
grid.
•
Isolate power prior to installation.
All models are fitted with a control box with cable glands & terminals and 10 m cable
•
Follow the instructions as stated under the previous heading 'General'.
•
Ensure that the cable gland fits the individual cable used with respect to clamping size
and type of cable. If not then apply a suitable cable gland and make sure that it is
approved for its application.
•
Connect an external earth wire to the external earth boss and ensure that this is
sufficiently connected to electrical ground.
•
The electrical power supply must be connected to the supplied power cable
•
For connecting the cable use an electrical isolating switch or a junction box which is
explosion-safe in accordance with the classification of its environment.
Installation manual AR-053 explosion-safe rooftop air conditioning system