Do not install the air conditioning unit in an environment where prolific charge generating
mechanisms (e.g. pneumatic transfer of powders, charge spraying in the powder coating
process) are present to avoid high levels of surface charge on the units plastic covers.
E
•
Either decommission the air conditioning unit or do not use it when it is damaged.
•
During installation of the air conditioning unit national safety regulations must be
observed.
•
Only use the air conditioning unit under the environmental conditions for which it is
specified. Deviating environmental conditions can contribute to damage to the
equipment and may lead to possible danger to the life of the user.
•
Do not use the air conditioning unit at temperatures deviating from the specified ambient
temperature range.
•
An electrical isolating switch must be installed in the vicinity of the rooftop air
conditioning system which is explosion-safe in accordance with the classification of its
environment.
•
Pre-fuse the electric power supply in accordance with the power consumption of the air
conditioning system.
•
The air conditioning unit must not be opened in hazardous classified locations unless the
environment has been known to be non-hazardous or power is switched off.
•
Repairs may only be carried out by the manufacturer or by a person appointed by the
manufacturer.
•
Modifications to the equipment or changes to the design are not permitted.
•
The product may only be used for the function for which it is designed and shall be
maintained in a good and clean condition.
If these instructions are not followed the explosion safety of the equipment cannot be
guaranteed. The equipment could then endanger the life of the user and could cause the
ignition of an explosive atmosphere. Consequently, Artidor as the manufacturer will waive
any responsibility.
3.
Characteristics
The characteristics can be summarized as follows:
•
Equipped with a H07RN-F 3 x 2,5 mm² connection cable, length 10 meter
•
Manufactured on the basis of European Directive 2014/34/EU (ATEX 114)
•
Suitable for use in gas hazardous areas classified as zone 2
•
Explosion safety category and protection against ignition applied:
II 3G Ex ec h ic mc IIB+H2 T3 Gc
•
Protection degree against ingress of water and dust IP56
Installation manual AR-053 explosion-safe rooftop air conditioning system
6 / 44
11-2024