Certification
cULus
UL "Marking"
Use 60°/75°C copper (CU) conductor and wire size range 18-12 AWG, stranded or
−
solid.flat surface of a Type 1 Enclosure.
INTRODUCTION The DCRJ-F regulator is a special version of the DCRJ power factor
controller especially designed for real-time static power factor compensation. It is
equipped with a total of 12 outputs, 11 static outputs with SSR (solid state relay) and one,
the last, with a standard electromechanical relay with changeover contact. A dedicated
software allows to react very fast to load variations, modifying the output configuration to
compensate the reactive power in the shortest time possible. All the measurements
(voltage, current, power etc) are sampled and recalculated in a time of about 20ms. The
reaction time of the controller after a load variation can vary from 40 to 60ms. See
technical characteristics for a more detailed description. It is also possible to configure the
device to control a 'mixed' configuration, that is with some static steps together with some
electromechanic steps in the same panel.