The manual configuration of the steps is maintained even when voltage is removed.
When power returns, the original state of the steps is restored.

1.17 AUTOMATIC OPERATION

In automatic mode, the controller calculates the optimum configuration of the reach to
achieve the set cosφ value.
The selection criteria take into consideration many variables such as: power of each step,
the number of operations, the total time of usage, reconnection time, etc.
The controller displays the imminent connection or disconnection of the step by the AUTO
LED flashing. The LED flashing can last in cases when the connection of a step is not
possible because of the reconnection time (i.e. capacitor discharge time).

1.18 KEYPAD LOCK

A function to exclude all modification to operating parameters can be enabled; measure-
ment viewing is still provided in any case.
To lock and unlock the keypad, press and keep MODE key pressed. Then press the + key
three times and the - key twice and after that release MODE. The display will view LOC
when the keypad is locked and UnL when it is unlocked.
When the lock is enabled, it is not possible to make the following operations:
Operation between automatic and manual mode
Access to set-up menus
Change of cosφ set-point
Clearing of MAX values.
By attempting to conduct the above operations, the display will view LOC to indicate the
locked keypad state.

1.19 ADVANCED MENU SET-UP

With the controller in MANU mode, press the MODE key for at least 5 seconds.
The wording SEt will be viewed to indicate the access to basic menu parameters. At this
point, simultaneously press the + and - keys for 5 seconds until Ad.S appears on the
display to indicate the access to advanced menu parameters.