4.Installation Preparation
2. Ensure that protective end caps are installed on all unused AC connectors. Unused AC harness
connectors are energised when the system is powered up.
3. AU-1P300/350/4002G supports up to maximum 11 units branch. AU-1P6002G supports up to
maximum 6 units branch. AU-1P8002G supports up to maximum 5 units branch. AU-1P10002G
supports up to maximum 3 units branch. AU -1P1600/20002G supports up to maximum 2units branch.
4.4 Precautions
The equipment is installed based on the system design and the location .
The installation must be done with the equipment disconnected from the grid (power disconnect
switch open) and with the PV modules shaded or isolated.
Make sure the environmental conditions of the microinverter's requirement (degree of protection,tem
perature, humidity, altitude, etc.) as specifed in the Technical Data section.
Avoid direct sunlight to prevent power derating which can be caused by an increase in the internal
temperature of the micro inverter.
Keep the inverter in well-ventilated place to avoid over heating.
Keep the inverter away from gases or fammable substances.
Avoid electromagnetic interference because it can compromise the normal operation of electronic
equipment.
Installation location shall meet the following conditions:
Install only on structures specifcally designed for PV modules (supplied by installation technicians).
Install microinverter underneath PV modules to make sure it works in the shadow. Nonobservance
may cause the derating of inverter production.