LOCATION OF THE UNIT
Select a location so that:
• The fresh air inlet from the outside is placed a minimum of ten feet from any other exhaust vent
• The two ducts to the outside are as short and straight as possible for the best system performance
• The door can be opened to clean the core and filters conveniently. Provide clearance at front of unit for service access to the blowers,
filters and energy exchange core (22 3/4" min. for full door swing)
• The exhaust outlet to the outside and fresh air inlet from the outside of the building should be at least ten feet apart to avoid cross-contamination.
The exhaust duct should be about the same length as the fresh air duct
• The exhaust outlet should not dump air into an enclosed space or into any other structure
The preferred mounting location for the unit is on a concrete structure because a concrete structure isolates any blower vibration.
If a basement area is not available or practical, use other mechanical room space such as a closet, garage, storage, or accessible attic
or crawl space.
NOTE: If you locate the unit in an attic or other unconditioned space, all of the unit's ductwork that is located in the attic must be insulated. Use at least
R-6 insulation.
INSTALLATION
CAUTION
RISK OF INJURY WHEN LIFTING AND INSTALLING UNIT OVERHEAD.
GET A HELPER AND WEAR EYE PROTECTION AND GLOVES.
Install the unit for the simplest duct layout and connections. Note however that the door is equipped with hinges. For the homeowner's convenience it
is helpful to install the unit so that the door does not fall off when it is unlatched.
PREPARATION
Mount the 4 brackets to the unit as illustrated in fig.1, using two screws provided for each
bracket through the two appropriate holes.
NOTE: Unit may be installed in any orientation. Be careful as condensation could be
present when outdoor temperature is low.
INSTALLATION - WALL MOUNT
1.Make sure there is enough space in front of the machine when installing so that the door
can be opened freely for maintainance. The minimum space is 26.7 inches.
2.The distance between brackets is 30.3 inch. Choose the appropriate place to locate the
unit
3.Screw half way two provided screws on the joist, the distance of two screws is 30.3
inch.
NOTE: The two screws should be horizontally aligned.
4.Hang the unit on the screws mounted on the joist using the larger holes of the
brackets with control box facing down. Secure the unit to the joist by fixing one screw
through the smaller hole in the each of the bottom brackets.
fig.1
fig.2
fig.3
fig.4
4
II
brackets
26.7"
30.3"
www.ortechindustries.ca