Device status
The device status is indicated by two colour changing LEDs on
the front of the unit, as shown in the table below.
State
Indication
Alarm
Flashing red LEDs [1]
Fault
Flashing yellow LEDs
Communicating
Flashing red LEDs
[1] This may also indicate an active Locate Device command from the
control panel.
Maintenance and testing
Maintenance
The unit should be maintained and tested according to local or
national requirements and any other applicable regulations. Do
not modify internal wiring or circuitry.
Testing
To activate an alarm, push the resettable element or turn the
key clockwise (one click). To reset the device, turn the key
anticlockwise (one click). Reset the control panel after testing.
Replacing the resettable element
Replace the resettable element (or add the breakable element)
as follows:
1.
Unlock and remove the front cover as described in
"Installation" on page 2.
2.
Push the element up, and then pull it out (see Figure 5).
3.
Replace the resettable element (or add the breakable
element, if required).
4.
Replace the front cover.
Analogue values
Analogue values for diagnosing and troubleshooting device
status are shown in the table below.
Value
Device Status
88
Normal
148
Alarm
Analogue values for diagnosing and troubleshooting reference
group, polling group, and device type are shown in the table
below.
Reference Group Polling Group
Value
197-226 (212)
P/N 03-0210-501-2300-05 • ISS 03NOV23
Device Type
197-226 (212)
197-226 (212)
Specifications
Electrical
Operating voltage
Current consumption
Standby
Alarm
Mechanical and environmental
IP rating
Backbox cable knockouts
Back
Top/bottom [1]
Wire size
Minimum
Maximum
Operating environment
Operating temperature
Storage temperature
Relative humidity
Colour
Red
Green
White
Material
Body
Contacts
Weight
Without backbox
With backbox [2]
Dimensions
Without backbox
With backbox [2]
[1] Top/bottom location subject to installation orientation.
[2] Backbox not supplied.
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Conformity
Notified/Approved body
Manufacturer
Year of first CE marking
Declaration of
Performance number [1]
16 to 20.5 VDC
250 µA
280 µA
IP41
1 × Ø 20 mm
1 × Ø 27 mm
2 × Ø 22 mm
0.13 mm² (0.40 mm)
3.31 mm² (2.05 mm)
−25 to +72°C
−25 to +72°C
10 to 95% (noncondensing)
RAL3028
RAL6024
RAL9003
ABS, PC, PMMA, POM
Nickel plated H59, tin plated
QSn6.5-0.1, tin plated H65
110 g
165 g
87 × 87× 26 mm
87 × 87× 57 mm
0370
Carrier Safety System (Hebei) Co. Ltd.,
80 Changjiang East Road, QETDZ,
Qinhuangdao 066004, Hebei, China.
Authorized EU manufacturing
representative:
Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
2022
03-0210-360-3083