JRG JRGURED 1300 Notice D'utilisation Et D'entretien page 29

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Operating range
The pressure- reducing valve JRGURED is
ap proved for the following operating ranges:
JRG Code
PN
kPa/bar
1300/1303 2'500/25
1310
2'500/25
1320
2'500/25
1330
2'500/25
Identification
– ½–2 ½ (GN/valve size)
– JRGURED (name of the fitting)
– JRG (manufacturer's trademark)
– Flow direction arrows
Seals made of AFM 34 should never be
used with grease or oil.
(AFM = Asbestos Free Material)
p
t
sec
max
kPa/bar
deg C
200–600/2–6
30
200–600/2–6
70
50–200/0.5–2
70
600–1'000/6–10
70
Factory setting
The pressure-reducing valve JRGURED are set at
the factory to the following secondary pressures:
JRG Code 1300/1303
JRG Code 1310
JRG Code 1320
JRG Code 1330
Other pressure settings on request.
Operating and maintenance instructions
Before commissioning the pres sure-
reducing valve, the inlet line has to be
thoroughly flushed out.
Commissioning:
Slowly open the shut- off valve upstream
of the pressure- redu cing valve.
The pressure -reducing valve JRGURED
is ready for operation.
400 kPa / 4 bar
400 kPa / 4 bar
200 kPa / 2 bar
600 kPa / 6 bar
E
29

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Jrgured 1303Jrgured 1310Jrgured 1320Jrgured 1330

Table des Matières