08
EN
02.03
Technical data
Power supply
Electrical power in dehumidification mode
Electrical power in dehumidification with cooling mode
Maximum current consumption
Switch-on current (LRA)
Air flow rate at fan speed Min (3) and 25 Pa counterpressure
Maximum counterpressure at 220 m³/h (fan speed Min (3) / Med (2) / Max (1))
Refrigerant R134a
Operating range – temperature
Operating range – relative humidity
Dehumidification capacity in dehumidification mode
Dehumidification capacity in dehumidification with cooling mode
Cooling capacity in dehumidification with cooling mode
Water-side capacity in dehumidification mode
Water-side capacity in dehumidification with cooling mode
Water flow rate
Pressure loss in the water circuit at 220 l/h
Dimensions (L x H x W)
Weight with filled water circuit
1)
Air: 25 °C, 65% relative humidity / water: 16 °C, 220 l/h / fan speed: Min (3) / counter-pressure: 25 Pa
2)
Dehumidification capacity and cooling capacity measured according to DIN EN 810 and DIN EN 1397
Vent valve
1
Condensation drain 16 mm
2
Water Return 3/8" M
3
Water Supply 3/8" M
4
Cable bushing
5
Electronics box with display
6
Air outlet
7
Air inlet with air filter
8
1)
1)
1), 2)
1), 2)
1), 2)
1)
1)
164
1
2
134
108
7
22
230 V AC, 50 Hz
490 W
430 W
3.6 A
20.0 A
270 m³/h
35 Pa / 50 Pa / 65 Pa
270 g
10–32 °C
45–98 %
22 l/d
24 l/d
1300 W
1230 W
1730 W
220 l/h
25 kPa
814 mm x 260 mm x 761 mm
48.1 kg
3
6
4
5
771
814
8
Ø10
238
260