Connect the power supply (230 V, AC, single-phase,
50 Hz) to the terminals phase L, neutral N and
protective earth PE of the machine as shown in the
illustration.
Potential-free contacts are provided for the controlinputs
of the machine. Connect the corresponding wires to
the terminal as shown in the illustration. There are
three different input signals:
▪ DH: Request for air dehumidification
▪ TC: Request for air dehumidification with cooling
▪ VENT: Request for continuous fan operation
The REHAU control system NEA SMART 2.0 can be
used to control the dehumidifier. For correct connection
and correct use, observe the relevant technical
information and the locally applicable regulations.
If required, the REHAU actuator UNI 230 V, which is
assigned to the water circuit of the dehumidifier, can
be connected to the terminals of the ZONE VALVE
output signal. When using an on-site actuator, please
RED
ensure that the nominal data of this actuator match
the output signal 230 V AC 1 A Max of the
dehumidifier.
Use separate cables for the power supply, the input
signals and the output signal and the cable glands
provided at the factory for this purpose. If three cable
glands are required for this, an additional cable gland
must be installed on site at the location of the cable
grommet. The factory-fitted cable glands are suitable
for cables with an outer diameter of 6 – 12 mm.
EV2
030039
Before using the unit, the electronics box cover must
Solenoid valves
be properly closed again.
T1 T2 T3
GA
RC
LPS
HPS
FLOAT
GREY
R.G.A
K50
030252
E.V.
ORANGE
PUMP
RED
F. PUMP
FAN
PURPLE
EV1
030039
External
4
Connections
Voltage and power supply
1
BLACK
GREY
Input signals (Digital 5 Vcc)
2
ORANGE
▪ DH
PURPLE
▪ TC
BLACK
▪ VENT starts ventilation
PCB
Output signal
3
BLUE
(optional, 230 V AC 1 A Max)
ZONE VALVE water circuit actuator
BLUE
On-site connections
4
BLUE
RED
COM
4
BROWN
5 A
FUSE
Autotransformer
FORBIDDEN TO USE
SPEEDS 4-5-6
DAMAGE THE
COMPRESSOR
Power Supply
1
230 V AC 1 Ph 50 Hz
Input
2
Digital 5 Vcc
DH
TC VENT
L
1 1 2 2
3
3
N
N
Hygrostat – starts dehumidification
Thermostat – starts dehumidification
with cooling
A1
B
NO
A2
NC
020045
6-
5-
4-
3-
MIN
Fan
2-
MED
MAX
1-
L-
020058
3
Output
(optional)
230 V AC 1 A Max
ZONE VALVE
5
BLACK
High
Pressure
Switch
NC
NO
Compr
050007