Télécharger Imprimer la page

PR electronic 9113 Manuel De Produit page 35

Publicité

LERBAKKEN 10, 8410 RØNDE DENMARK
Warning: To prevent ignition of the explosive atmospheres, disconnect power before servicing and do
not separate connectors when energized and an explosive gas mixture is present.
Warning: Do not mount or remove modules from the Power Rail when an explosive gas mixture is
Hazardous Classified Location
present.
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC
or Group IIC, [Ex ia Ga] IIC Gc
Intrinsically safe apparatus
entity parameters:
Vmax (Ui)  Vt (Uo)
Imax (Ii)
 It (Io)
Pi  Po
Ca  C
+ Ci
cable
La  L
+ Li
cable
The sum of capacitance and
inductance of cable and
intrinsic safe equipment must
be less or equal to Ca and La
Ex input
CH1 (terminal 42,43)
CH2 (terminal 52,53)
Vt (U
):
17.4 V
o
It (I
):
18.4 mA
o
P
:
80 mW
o
Lo/Ro
445 μH/
IIC /
IIB /
Group A,B
Group C,E,F
C
/ C
0.3  F
1.6  F
a
o.
L
/ L
80 mH
250 mH
a
o.
U
:
10 V
i
I
:
30 mA
i
C
:
15 nF
i
1.7 μH
L
i.
Revision date:
2019-04-04
Unclassified Location or
Hazardous Classified Location
Class I, Division 2, Group A,B,C,D T4
or Class I Zone 2 Group IIC T4 Gc
-20 ≤ Ta ≤ 60ºC
44
+
43
CH1
42
41
54
53
-
52
51
IIA /
Group D,G
8  F
600 mH
Version Revision:
V5 R0
9113-EMP - Version de produit 9113-004
4501
CH2
9113
91 92 93 94 95
Power
Rail
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
: 253 V, max 400 Hz
m
Prepared by:
PB
9113QF01
34
33
32
31
14
13
12
11
Page:
3/3
35

Publicité

loading

Produits Connexes pour PR electronic 9113

Ce manuel est également adapté pour:

9113a-emp9113a