E
lectrical Ratings
Table 4: SPST Electrical Ratings (P70A, B, C, and D, and P170A, C, and D Models)
Motor Horsepower
Motor Full-Load Amperes
Motor Locked-Rotor Amperes
Non-Inductive Amperes
Pilot Duty
Table 5: SPDT Electrical Ratings 1hp Switch (P70E and P170E Models)
Motor Full Load Amperes
Motor Locked Rotor
Amperes
Non-Inductive Amperes
Pilot Duty
*
Rating for P70EC models only
Table 6: SPDT Electrical Ratings 1/4 hp Switch (P70F and P170F Models)
Motor Full Load Amperes
Motor Locked Rotor
Amperes
Non-Inductive Amperes
Pilot Duty
Table 7: 4-wire, 2-circuit Electrical Ratings
(P70G, H, J, and K, and P170G, H, J, and K Models)
Motor Full Load
Amperes
Motor Locked Rotor
Amperes
Non-Inductive
Amperes
Pilot Duty (for both
sets of contacts)
P70, P72, and P170 Controls for Low Pressure Applications Product/Technical Bulletin
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
All manuals and user guides at all-guides.com
Standard Single-Phase Ratings
120 VAC
1.5
20
120
22
125 VA at 120 to 600VAC; 57.5 VA at 120 to 300 VDC
120 VAC
16.0
96.0
16.0
125 VA at 120 to 600 VAC
120 VAC
6.0
36.0
6.0
Line-M2 (Main Contacts)
120 VAC
208 VAC
240 VAC
16.0
9.2
8.0
96.0
55.2
48.0
16.0
9.2
8.0
125 VA at 24 to 600 VAC; 57.5 VA at 120 to 300 VDC
208 VAC
240 VAC
3
3
18.7
17
112.2
102
22
22
Standard Single-Phase Ratings
208 VAC
240 VAC
9.2
8.0
55.2
48.0
9.2
8.0
Standard Single-Phase Ratings
208 VAC
3.3
19.8
6.0
125 VA at 24 to 240 VAC
Standard Single-Phase Ratings
Line-M1 (Auxiliary Contacts)
277 VAC
120 VAC
--
6.0
--
36.0
7.2
6.0
Hermetic Compressor
Single-Phase Ratings
208/240 VAC
--
20
120
--
277 VAC*
7.0
42.0
-
125 VA at 24 to 600 VAC
240 VAC
3.0
18.0
6.0
208 VAC
240 VAC
277 VAC
3.3
3.0
19.8
18.0
6.0
6.0
6.0
--
--
11

Publicité

loading

Ce manuel est également adapté pour:

P72P170