Monitoring Box
Navigation for single phase Smart Meter:
Each successive pressing of the
1. Total active energy in kWh
2. Consumed active energy in kWh
3. Injected active energy in kWh
4. Voltage in V
5. Current in A
6. Power in W
WARNING: It is necessary to check that the Smart Meter is configured for a 100A current sensing
clamp. To do this, verify that the value of the input current (see navigation in the table above) is set to
"CT0100".
If this is not the case, restart the inverter (after taking the precautions related to disconnection) and
press the button until the Smart Meter display shows "-SET-". The inverter will automatically configure
the Smart Meter input current to "CT0100". This automatic configuration is only done during the first 5
minutes following startup of the inverter.
When the text "-SET-" disappears, verify again that the Smart meter is set to "CT0100".
Navigation for three phases Smart Meter:
Each successive pressing of the
selects a new value:
1.
Instantaneous Active Power in kW
2.
Instantaneous Reactive Power in kVAR
3.
Instantaneous Volt-amps in KVA
4.
Total kW, kVARh, kVA
5.
Frequency and Power Factor (total)
6.
Power Factor of each phase
7.
Maximum Power Demand
Each successive short pressing (lasting less than 3s) of the
1.
Total active energy in kWh. Total kWh=imported +exported (kWh)
2.
Total Imported active energy in kWh
3.
Total Exported active energy in kWh
4.
Total reactive energy in kVARh. Total kVARh=imported +exported (kVARh)
5.
Imported reactive energy in kVARh
6.
Exported reactive energy in kVARh
Installation_Manual_Monitoring_Box_
IMA-BOX
button selects a new range:
button
Each successive pressing of the
selects a new value:
7. Frequency in Hz
8. Power factor
9. Modbus address
10. Baud Rate
11. Parity
12. ratio
1.
Phase to neutral voltages (V)
2.
Phase to phase voltages (V)
3.
Current on each phase (A)
4.
Neutral current (A)
5.
Maximum Current Demand (A)
button selects a new vaue:
_VA.6
IMA-BOX
FR
EN
button
29