Honeywell H1008A,D Installation Instructions
Honeywell H1008A,D Installation Instructions

Honeywell H1008A,D Installation Instructions

Hygrostats automatiques

Publicité

Liens rapides

APPLICATION
The H1008A,D Automatic Humidity Controls with
HumidiCalc+™ Software are duct mounted and provide
automatic, low voltage, electronic control of by-pass
flow-through, powered flow-through, steam and drum
humidifiers in central heating systems. The H1008D also
controls heat/energy recovery units and dehumidifiers.
The H1008A,D are designed to automatically adjust the
humidity level based on indoor temperature and humidity,
inferred or measured outdoor temperature and the
frost factor dial setting. The frost factor setting is used to
maintain a comfortable humidity level in the home while
reducing moisture condensation on inside windows. The
HumidiCalc+™ Software infers the outdoor temperature
by monitoring equipment cycles and eliminating the need
for an outdoor temperature sensor when used with gas or
oil furnaces. Using the C7089H Outdoor Temperature
Sensor (purchased separately), the H1008A,D also
provide automatic humidity control for heat pump
systems.
American Lung Association Health
House Program and Honeywell Working
Together For Better Air
Did you know that the average person breathes 3400
gallons(12,870 liters) of air each day * and spends 90%
of that day inside?**
Indoor air quality products from Honeywell are designed
to help make your home more comfortable—from zoning
products that allow you to control the temperature in
individual areas of the home to humidifiers and comfort
control centers that help balance the moisture content of
your indoor air.
Honeywell is proud to be a partner of the American Lung
Association Health House program, contributing annually
to the Lung Association. The Health House program
provides guidelines for constructing homes with
improved air quality and ventilation.
For more information on ways to improve the air inside
your home, please visit the Health House website at:
www.healthhouse.org,
® U.S. Registered Trademark
Copyright © 2003 Honeywell International Inc. •
Automatic Humidity Control
• All Rights Reserved
INSTALLATION INSTRUCTIONS
the American Lung Association website at:
ww.lungusa.org, and the Lung Association website in
Canada: www.lung.ca or www.poumon.ca.
The American Lung Association and its Health House
program do not endorse products.
For more information about Honeywell Indoor Air Quality
products, visit:
www.honeywell.com/yourhome, or call
1-800-345-6770 x531.
*EPA.National Air Quality 1999 Status & Trends.
**Indoor Air Pollution, An Introduction for Health Professionals, EPA, US
Government Printing Office #1994-523-217/81322.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to
follow them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions to make
sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
Use the following specifications for this installation:
Electrical Ratings:
Power Supply: 24 Vac, 60 Hz.
Humidifier Control Relay Contacts:
Inductive: 2A full load, 10A locked rotor.
Resistive: 2A.
Thermostat/Furnace Load: 11 mA maximum at 24 Vac.
CAUTION
Voltage Hazard.
Power supply can cause electrical shock.
Disconnect power supply before beginning
installation.
H1008A,D
69-1185EF-3

Publicité

loading

Sommaire des Matières pour Honeywell H1008A,D

  • Page 1 Inductive: 2A full load, 10A locked rotor. Resistive: 2A. Honeywell is proud to be a partner of the American Lung Thermostat/Furnace Load: 11 mA maximum at 24 Vac. Association Health House program, contributing annually to the Lung Association. The Health House program...
  • Page 2 FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM). M12827 Use the following procedure to mount the H1008A,D in the return air duct: Fig. 4. Correct wiring technique. 1. Remove the cover by placing your thumb in the bottom notch between the cover and the base and C7089H Outdoor Temperature Sensor pulling out and up.
  • Page 3 COM terminals on the H1008A,D. 2. Connect the humidifier to the two HUM terminals All wiring must comply with applicable local codes, on the H1008A,D as shown in Fig. 5 through 8. ordinances and regulations. 3. In furnace systems with two transformers, connect...
  • Page 4 H1008A,D AUTOMATIC HUMIDITY CONTROL DO NOT REMOVE FAN TIMER JUMPER UNLESS BOARD YOU ARE USING AN OUTDOOR TEMPERATURE DEHUM SENSOR DEHUM (OPTIONAL) SYSTEM COMMON (REQUIRED) (REQUIRED) TWO YELLOW WIRES TEST 24VAC WIRE H1008 IN PARALLEL TWO RED WITH FAN TIMER BOARD...
  • Page 5 H1008A,D AUTOMATIC HUMIDITY CONTROL STEAM HUMIDIFIER OPTIONAL OUTDOOR HUMIDISTAT AIR SENSOR ROOM THERMOSTAT TERMINALS DEHUM TO SYSTEM FAN DEHUM WIRING TEST 24 VAC FURNACE (HOT) TRANSFORMER FROST HEAT FACTOR AUTOMATIC HUMIDITY CONTROL RELAY SETPOINT (HOT) DIAL POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD ISOLATED RELAY CONTACTS.
  • Page 6 OVERLOAD PROTECTION AS REQUIRED. by one setting. IN SINGLE TRANSFORMER SYSTEMS, JUMPER CG AND CW. M13307 The H1008A,D Automatic Humidity Control with Fig. 9. Wiring for two-transformer system. HumidiCalc+™ Software is designed to provide an optimal 50°F (10°C) dewpoint. It automatically adjusts...
  • Page 7 H1008A,D AUTOMATIC HUMIDITY CONTROL ERROR STATUS To troubleshoot the system where error status is IMPORTANT indicated: — When an outdoor sensor is not installed, there • If an outdoor temperature sensor is not used: may be a delay in humidification, caused by the —...
  • Page 8 H1008A,D AUTOMATIC HUMIDITY CONTROL Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 Printed in U.S.A. on recycled 69-1185EF-3 G.H. Rev. 7-03 www.honeywell.com/yourhome paper containing at least 10%...
  • Page 9 90 % du temps à l’intérieur**? que celui-ci correspond bien à l’application prévue. 3. L’installateur doit être un technicien d’expérience Les produits de Honeywell pour la qualité de l’air ambiant ayant reçu une formation pertinente. sont conçus pour vous aider à rendre votre maison plus 4.
  • Page 10 MF12827 Fig. 4. Comment raccorder les fils correctement. Suivre ensuite les étapes ci-dessous pour installer le H1008A,D dans la gaine de reprise. 1. Retirer le couvercle en plaçant le pouce dans Capteur de température extérieure l’encoche du bas entre le couvercle et la base, et C7089H tirer vers soi et vers le haut.
  • Page 11 électrique et des blessures. 2. Raccorder l’humidificateur aux deux bornes HUM Couper l’alimentation avant de procéder à des H1008A,D, comme l’illustrent les Fig. 6 à 10. l’installation ou à l’entretien. 3. Dans les systèmes de chauffage à deux transfor- mateurs, raccorder CG au commun du transforma- Tout le câblage doit être conforme aux codes et...
  • Page 12 HYGROSTATS AUTOMATIQUES H1008A,D NE PAS RETIRER LE CAVALIER SAUF SI ON UTILISE UN CAPTEUR DE TEMPÉRATURE EXTÉRIEURE BORNIER DE LA MINUTERIE DU VENTILATEUR DEHUM DEHUM (OPTIONNEL) COMMUN DU SYSTÈME (REQUIS) (REQUIS) DEUX FILS TEST 24VAC JAUNES RACCORDER LE H1008 DEUX FILS EN PARALLÈLE AVEC LES...
  • Page 13 HYGROSTATS AUTOMATIQUES H1008A,D CAPTEUR DE HUMIDIFICATEUR À VAPEUR TEMPÉRATURE EXTÉRIEURE HYGROSTAT EN OPTION THERMOSTAT D’AMBIANCE BORNES DEHUM VERS LE VENTILATEUR DEHUM DU SYSTÈME RACCORDEMENT AU VENTILATEUR TEST 24 VAC TRANSFORMATEUR L1 (SOUS DE L’APPAREIL DE CHAUFFAGE TENSION) BOUTON RELAIS DE V c.a.
  • Page 14 HYGROSTATS AUTOMATIQUES H1008A,D RÉGLAGES HYGROSTAT AUTOMATIQUE H1008 Ajustement TRANSFORMATEUR - Pour ajuster le facteur de givre, régler le bouton du facteur de REFROIDISSEMENT givre à 10 et consulter le Tableau 1 pour savoir comment L1 (SOUS TENSION) ajuster le facteur—d’un cran à la fois—en augmentant le point...
  • Page 15 HYGROSTATS AUTOMATIQUES H1008A,D ÉTAT DU SYSTÈME Sur le régulateur, un voyant vert clignotant indique l’état du système. La fréquence de clignotement représente l’état du Tableau 3. Modes d’erreur. système. Voir le Tableau 2 pour obtenir une description. Capteur Erreur indiquée lorsque…...
  • Page 16 19.9 12.5 10.0 8.04 Température (°F) Température (°C) Solutions de régulation et d'automatisation Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35, Dynamic Drive Golden Valley, MN 55422 Scarborough (Ontario) M1V 4Z9 Imprimé aux États-Unis sur du papier 69-1185EF-3 G.H.