EN
FOTO
Safety input with NC contact. During closure, when the photocell ray is interrupted, it immediately opens the gate again.
If this input is kept open by a clock or weekly timer, the automation system closes again after the pause time, if programmed,
and only once the entrance is clear.
STOP
NC safety input. When this is activated it stops the automation instantly and when a start command is then given the gate
will always open. If a stop command is given during pause time it eliminates automatic re-closing, waiting for a command, or
close after 2 minutes regard DIP 5 setting.
START
NO input, allowing the open and close signals to be sent to the automation system. This input is ignored during the opening cycle.
If this input is commanded continuously, the automation system performs the opening cycle and, if the pause time is pro-
grammed and only once the entrance is clear, the automatic closing cycle.
AP.PD.
The command is accepted only if the barrier is completely closed, and automatic closing is temporarily disabled during the
opening cycle. Use in accordance with the automatic logic of the start command (DIP 1-2 ON).
APRE
Do not use (see paragraph 12)
CHIUDE
NO input for closing. To close the automation only if the safety devices have not triggered.
7. DIP SWITCH CONFIGURATION
Dip switches 1 and 2: They select the functioning logic
Off -Off : Hold-to-run logic.
The automation works by keeping the commands pressed, acting on the open or close inputs.
The start command opens once and closes once.
Commands via radio in the hold-to-run logic are forbidden by law.
On-Off : SEMI-AUTOMATIC (Logic for pulse type collective control)
Open command only. To close after opening, press start or close. Pressing during closing cycle reopens the barrier.
On-On: AUTOMATIC (Logic for pulse type collective control)
Open command only. Pressing start when paused closes barrier, pressing while barrier is closing opens barrier. Barrier is closed
after pause time.
Dip switch 3: Selects pre-fl ashing function.
Off :
The pre-fl ashing function is disabled: the fl ashing unit is commanded during the manoeuvre.
On:
The warning lamp fl ashes for a period from 2 to 10 seconds (settable from trimmer PM1) before all manoeuvres except barrier
inversion triggered by the safety devices.
Dip 4: Selects output function OUT 1-2-3 (see paragraph 6.1)
Off :
TWIN
On:
TWIN LIGHT
Dip 5: After STOP behavior
Off :
In AUTOMATIC logic, after a STOP, the automatic re-closing is inhibit.
On:
In AUTOMATIC logic, after an occurred STOP, the automatic re-closing is done after 2 minutes from the STOP deactivation,
regardless the pause time set on PM3.
Dip 6-7-8: NOT IN USE
8. PROGRAMMING
To guarantee the safety of the system, remember that the automation must be checked according to the risk analysis, therefore the installer
must install any safety accessories needed and resolve all residue risks and dangers that the machine may cause when it works automatically
via the remote controls.
Control unit
M2
6.2
INPUTS CONTROL TERMINAL BLOCK
8.1 PRELIMINARY CHECKS
- 12 -