Analogue input for adjusting the current during welding
G
REG I
by ± 15%.
Examples of PLC consoles:
TIG current source
F
E
D
A
G
B
C
HELP WITH UNDERSTANDING AND WIRING
START
START = 0 : the welding cycle is started with the JOB selected. Changing the JOB will have no effect during welding. When ARC ON = 0 is received,
the welding arc is lit. START = 1: the welding cycle ends (DownSlope ... PostGas). When ARC ON = 1 is received, the welding arc is switched off.
If the default context is selected (JOB0), the HMI parameters can be accessed without welding.
Regardless of the JOB or context selected, the current is always adjustable via the potentiometer (REG I).
PROG
Example of a resistance network:
VCC
10k
R1
R2
R3
R4
R5
GND
Translation of the original
instructions
Automation with potentiometer
Vext
R_PU
ARC ON
AUTODETECT
START
VCC
REG I
PROG
GND
Value proposition for resistors:
R1 : 1 kΩ
R2 : 3.3 kΩ
R3 : 6.8 kΩ
R6
R4 : 15 kΩ
R5 : 33 kΩ
R6 : 100 kΩ
In position 1/2/3/4/5 :
REG I = 5V = 0% variation,
REG I = 0V -> -15% variation
REG I = 10V -> +15% variation
If POSITION 0, then the variation occurs over the entire
current range permitted by the product.
Automation with resistor network
Vext
R_PU
U
GND
CONNECT 5
U
5