Room Temperature – Direct Plug In
5.3
As an option you can plug in a room thermostat to the ClimaticControl-HC. Direct plug in of a room thermostat op-
timizes the operational time of the circulation pump and even the supply flow temperature depending on the condi-
tions in the main room.
5.3.1
Mixed circuit (Water Floor), standard room thermostat, wired type
If a wired type of a standard room thermostat is plugged in and the preset room temperature is reached in
the room, the under floor circulation pump switches off after pump delay time. (PUMP: System parame-
ters: pump delay time)
5.3.2
Direct circuit (Panel Heater), standard room thermostat, wired type
If a second circulation pump is installed and managed by the ClimaticControl-HC (Inst: System param-
eters: installation type, "2P.x"), you can install a second wired room thermostat to manage the working of
the high temperature pump.
This pump will work in the following way: If the preset room temerature is reached in the room the High
water temperature circulation pump switches off after pump delay time. (PUMP: System parameters:
pump delay time)
WFHT-LCD
WFHT-BASIC
4 4 2 1
L
N
Output
TH
WFHT-LCD
WFHT-BASIC
4 4 2 1
L
N
Output
TH
7
MILUX xxx
< °C
Fig. 6
MILUX xxx
< °C
GB
Fig. 7