How can the adjustments be changed?
The procedure for changing the parameters having changed the code 000 to code 111.
Is the same for all programmable values (S1, S2, Hyst, Filter, Output analogue...).
If you want to change an adjustment the ring-gap has to be turned to Pos. 2.
If you want to jump to the next value or to the next menu, the ring-gap has to be turned to Pos. 1.
Important: If a change or adjustment has to be entered then the ring-gap has to be turned to Pos. 1
in order to close the procedure.
Programming protection:
To prevent unintentional programming, the programming ring can be removed or it can be positioned in
reverse (rotate by 180° / PROG LOCK upwards).
Technical data SW-600-...-IL
Technical data
Measuring range, depended on material
Repeat accuracy
Switching point, Hysteresis
Type
Art.-No.
Process connection
Operating voltage (U
)
B
Permitted residual ripple max.
Analog output
Switching outputs
No-load current (I
)
o
Response- time
Temperature gradient
Operating pressure
Permitted ambient temperature
Display
Degree of protection IEC 60529
Connection
Material in contact with medium
Housing
Glass
Magnet
14
All manuals and user guides at all-guides.com
SW-600-M12/28-IL
544 100
M 12 X 1
4(0) - 20 mA, 2(0) - 10 V with 500 Ohm
PNP, NPN / max 300 mA in total
LCD Display (32 x 16 pixel), LED red
Plug-in connector M 12 x 1, 5 pole
1 - 300 cm / s (H
O: 150 cm / s)
2
1 %
Adjustable
SW-600-G1/4"/28-IL
544 120
G 1/4"
18...30 V DC
10 %
Typ. 60 mA
Typ. 2 s
Typ. 4 K / s
200 bar
0...+70 °C
IP 67
Stainless steel no. 1.4571 (VA)
Stainless steel 1.4504 (VA)
Mineral glass tempered
Cobalt Samarium
SW-600-G1/2"/28-IL
544 140
G 1/2"