6.
Marking
The warning lights comply to the European Directives for EMC and ATEX and implicit to the
Low Voltage Directive. With regard to explosion safety the warning lights have been
E
designed and manufactured on the basis of the essential health and safety requirements of
European Directive 2014/34/EU (ATEX 114) relating to Group II Category 2GD. Harmonized
European construction standards have been applied fulfilling the essential requirements of
the directives. Please refer to chapter 5 'Technical data" and the EU Declaration of
Conformity at the last page of this user manual for more details.
II 2 G Ex mb IIC T4 Gb
II 2 D Ex mb IIIC T135 ºC Db
Cert. DEKRA 24ATEX0038 X
IECEx DEK 24.0027 X
Artidor Explosion Safety B.V., Emopad 38, 5663 PB Geldrop
The Netherlands, +31(0)40 7873911, https://www.artidor.com
Example of an AR-048 warning light label
Warning
To avoid electrostatic charge clean only with a
damp cloth. Do not use solvents.
Permitted supply short-circuit current: 50 A
The AR-048 warning label
7.
Installation instructions
•
Installation of explosion-safe equipment such as this product must be carried out by
personnel specially trained and qualified to do this, following the relevant requirements
of the installation standard EN 60079-14.
•
For the installation and use of this product the relevant safety regulations and also the
generally recognized latest state of the technology apply.
•
During assembly, care must be taken that the framework, screws and surface are strong
enough to take the weight of the warning light.
•
Isolate power from the electrical supply cable prior to installation.
Installation manual AR-048 LED warning light
8 / 36
2813
AR-048/031 Yellow
24 - 48 VDC, 4 Watt
IP65
Year: 2024
-20 °C < Ta < +60 °C
Lot & S/N: AS249999
05-2024