4 Assembly and connection
Risk of damage!
GB
Stability of the cooling unit is only
guaranteed in its assembled state.
Brace the rear enclosure half to prevent
it from falling over before removing the
front enclosure half.
• Loosen the four nuts on the front enclosure half and
pull the enclosure forwards by approx. 5 cm.
• Loosen the flat-pin connectors of the PE conductor
between the two enclosure halves.
• Disconnect the fan connection.
• Remove the front enclosure tray completely.
Fig. 11: Remove the cover
• Remove the four spacer bolts.
• Cut the supplied sealing tape to the correct length
and stick it carefully along the inside of the rear
enclosure half so that no gaps are left at the
connection points.
Fig. 12: Attach the sealing tape
• Push the rear enclosure half into the mounting
cut-out and secure it with the four spacer bolts.
• Push the display cable through the cable gland of
the front enclosure half.
10
Fig. 13: Secure the cooling unit
• Connect the fan connector and PE conductor.
• Mount the front enclosure tray using the washers
and nuts.
Fig. 14: Connect the display connector
• Carefully connect the display connector.
• Push the louvred grille and, where applicable,
the infill panel, onto the enclosure.
Rittal cooling unit assembly instructions

Publicité