Télécharger Imprimer la page

hager VF112 Notice D'instructions page 5

Publicité

33
2
1
36
Attention!
It is critical that any enclosure is sized and selected to accomodate
and dissipate heat rise generated from all installed devices.
The table (right) provides maximum permissible heat dissipation for
each golf enclosure size. Please ensure that you calculate internal
heat generated from your installation and select the correct
enclosure accordingly.
15 %
Echelle : 25 %
Hager Industrial de Envolventes S.A., Alfred Nobel 18, 08430 LA ROCA DEL VALLES, SPAIN
34
A
B
VZ788N
37
35
VZ787N
1
Echelle 50 %
90°
Admissible thermal dissipation loss for flush
mounted distribution boards at temperarture rise ∆T*
Reference
10K
15K
W
W
VF104
2,5
4,1
VF108
2,8
4,6
VF112
4,4
7,2
6VF00100
VF212
5,7
9,5
Plastron marquage_01
VF312
7,1
11,7
VF412
8,7
14,4
VF118
5,8
9,6
VF218
7,6
12,6
VF318
9,2
15,3
VF418
11,2
18,5
VF122
6,8
11,2
*) ∆T is the temperature difference between the upper limiting
temperature of the installed equipment and the ambient air
temperature of the distribution board.
Echelle : 12,5 %
AI1_Golf_Porte_01
3
2
20K
25K
30K
W
W
W
5,9
7,7
9,7
6,5
8,6
10,8
10,4
13,7
17,2
13,5
17,9
22,4
15 %
16,8
22,1
27,8
20,5
27,1
34,0
13,8
16,2
22,8
17,9
23,7
29,7
21,9
28,9
36,2
26,5
35,0
43,9
16,0
21,1
26,5
AI1_Golf_porte_02
05

Publicité

loading

Ce manuel est également adapté pour:

Vf108Vf104Vf212Vf312Vf412Vf118 ... Afficher tout