Enclosure class
DIN top hat rail 35mm
Terminal screws
Height
Width
Depth
Cable length
phase monitoring
8
SE-E5
Protection functions and properties:
• Temperature monitoring
– The device locks out immediately when the preset motor winding temperature, discharge gas temperature or
oil temperature is exceeded.
• Monitoring of rotation direction, phase sequence and phase failure
– The rotation direction is monitored within the first 5 seconds after compressor start (operating recognition). If
the compressor starts with the wrong rotation direction during this time span, the protection device locks out
immediately .
– In the event of a phase failure between the 6th and the 10th second after compressor start, the device opens
the relay contact immediately and closes it again after 6 minutes.
In case of 3 phase failures within 18 minutes or in case of 10 phase failures/phase asymmetries within 24
hours, the protection device locks out immediately .
• Single phase failure and cable short-circuit monitoring
• Replaces the SE-E2.
• The previous models are fully exchangeable, with the same functionality and terminal assignment. Dimensions
and their integration into the control are also identical.
• Suitable for operation with frequency inverter.
• Complies with EN/UL 60730.
For relay current 24 V DC, see also information under Relay versions .
Technical data
Monitoring parameters
Winding temperature
Single phase failure winding temper-
ature
Cable short-circuit winding temper-
ature
Phases
Supply voltage versions
Version 1
CT-120-3 // PDF Download
SE-E4
Unit
IP00
x
x
80
mm
68,3
mm
32,5
mm
300
mm
SE-E5
Unit
x
x
x
x
59