Climatic Curves
Climatic Custom Curves
Parameters 112 and 117 set to 0 (see table 1) allows to load
in the control a custom climatic curve.
Below figures show which parameter of installer
par 4
par 4
NOTE:
When UI is installed (par 100 set to 3) or SUI Comfort mode is installed (par 100 set to 2), control is expecting the choice
between a custom or pre-set climatic curve. In case application requires fixed water set point in necessary to set an
horizontal climatic curve by setting par.120=121 for Heating Climatic Curve and 124=125 for Cooling Climatic Curve.
14
HEATING CLIMATIC CURVE
65
1
55
45
3
35
25
15
-15
-10
-5
Outside Temperature
COOLING CLIMATIC CURVE
20
1
15
3
10
5
0
15
20
Outside Temperature
configuration table need to be set to create customized
heating and cooling curves.
2
0
5
10
2
25
30
35
1. (Parameter No 121)
2. (Parameter No 120)
3. (Parameter No 118)
4. (Parameter No 119)
4
15
20
25
1. (Parameter No 125)
2. (Parameter No 124)
3. (Parameter No 123)
4. (Parameter No 122)
4
40
45