Battery Replacement
Under normal conditions, the original batteries in your UPS will last many years. See Safety section
before replacing batteries. The batteries are designed for hot-swap replacement (i.e. leaving the
UPS in ON mode), but some qualified service personnel may wish to put the UPS in the OFF mode
and disconnect equipment before proceeding. Note: Refer to the label on the battery retention
plate for the R.B.C. part number.
SMART3000RM2UP and SMART3000RMXL2U Battery (RBC58-2U)
Replacement Procedure
1
Remove Front Panel
1
4 x screws
2
Remove Battery Retention Plate
4 x screws
2
3
Disconnect Batteries
3
15-06-021-93-3088.indb 18
4
Remove/Recycle Batteries
First,
remove the left row of batteries.
4A
Then,
slide the right row of batteries to
4B
the left and remove.
4A
4B
18
6/3/2015 10:09:28 AM