INSTALLATION ADVICES
No electrical equipment should be
located in Volume 1.
No equipment or electrical connec-
tion should be located less than
60cm from the cabin (Volume 2).
The height required for the installa-
tion of the cabin must be minimum
2.25m.
Drainage: the drainage slope must
be 2cm per meter to facilitate the
flow of water.
It is recommended to continue the
evacuation with 40mm diameter
pipes.
Remember to leave a space behind
the cabin during installation. You
must have enough space to slip in
and make the drain connections.
Minimum distance needed around
of the cabin to carry out the installation
VOLUME 0: (IPX7) No electrical appliances (hair dryer, razor, smartphone, etc.) are allowed.
VOLUME 1: (IPX5) Installation of very low voltage electrical appliances (TBTS 12V).
VOLUME 2: (IPX4) All installed electrical devices must be Class II and comply with CE standards.
PRE-INSTALLATION INSTRUCTIONS
MIN
MAX
10cm
30cm
D
D1
CABINE
60cm
1/4
CERCLE
VOLUME 2
VOLUME 1
60cm
Minimum distance needed around
of the cabin to carry out the installation
NORME NF C 15-100
11
VOLUME 2
C
F
120cm
VOLUME 0
HOT WATER
C
COLD WATER
F
EVACUATION (Diameter=40mm)
D
Zone practical for the evacuation
D1
60cm
CABINE
RECTANGLE
300
cm
225cm