Operation
The input terminal block requires the connection of the phase conductors in a "star"
arrangement (3 phase conductors plus a neutral conductor). It is forbidden to connect
the phase conductors in the "triangle" system (three phase conductors without a
neutral conductor).
When connecting the phases, it is important to keep the correct sequence. Phase 1 to
1, 2 to 2, and 3 to 3. Otherwise, the safety system may disable the device.
The "bypass" switch is the bypass switch of the stabilizer. When the AVR is operating
normally, the bypass switch should be off. When the device is damaged, turn off the
device with the power button and turn on the BYPASS mode. The device will supply
energy directly from the grid, bypassing the AVR electronics.
When the delay button on the front panel is pressed, the device will delay the start for
180 seconds until the output signal is applied. The default time is 6 seconds.
The button "Single-phase mode / three-phase mode" is used to select the operating
mode. By default, the device is set to three-phase mode. Pressing the button will
switch the device to single phase mode.
In three-phase mode, the AVR will compensate for too high or too low an input voltage
and will output the stabilized voltage. If in this mode any of the phases does not work
properly or is not connected, the device will protect itself and will not supply voltage to
the output, informing about it by switching on the "PHASE ERROR" indicator.
In single-phase mode, each phase can work independently, e.g. an error in phase 2
operation will not affect the operation of phase 1. The input voltage of each phase is
stabilized with 3% precision. The maximum power on each phase is approx. 1/3 of the
maximum nominal power of AVR (10KW).
Cleaning
Clean this device with soft, dry cloth. Do not use any chemical agents to clean this
product. Before cleaning, make sure the device is switched off and disconnected from
the power supply.
EN
16
Owner's manual
Owner's manual
Specification
10000 VA
Rated power
Input voltage range
225 - 450 V
Minimum starting voltage
225 V
Minimum output voltage
310 V
Output voltage range
400 V
Phases
1 / 3 phases
Stabilization accuracy
± 3%
Efficiency
98%
Stabilization control
servo motor
Transformer
C.R.G.O. toroidal
Indicator
LCD display
Operating frequency
50 / 60 Hz
Start delay switch
6 / 180 s
Housing material
steel
Operating temperature
0 – 40°C
Relative humidity
10 – 102%
Storage temperature
-15°C – 45°C
Protections
overload, short circuit, over/low voltage, overheating
Cooling start
at 30% of rated power
Cooling off
at 20% of rated power
Dimensions
545 x 230 x 397 mm
Weight
31 kg
English
Correct Disposal of This Product
(Waste Electrical & Electronic Equipment)
(Applicable in the European Union and other European countries with separate collection systems) This marking
shown on the product or its literature, indicates that it should not be disposed with other household wastes at the
end of its working life. To prevent possible harm to the environment or human health from uncontrolled waste
disposal, please separate this from other types of wastes and recycle it responsibly to promote the sustainable reuse
of material resources. Household users should contact either the retailer where they purchased this product, or their
local government office, for details of where and how they can take this item for environmentally safe recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract. This
product should not be mixed with other commercial wastes for disposal.
Made in China for Lechpol Electronics Leszek Sp.k., ul. Garwolińska 1, 08-400 Miętne.