ENGLISH
The temperature controllers of all the showcases are blocked so that the user cannot set lower temperatures than those planned
PARETE VINO +3 ° C (excluding P * VBR10 and CAR10-20 +12 ° C) TECA +4 °C (excluding TC10-20 +12 °C). It is not allowed to
enter the hidden parameters and modify these values. The showcases are not designed and built to operate at low temperatures.
Failure to comply with this provision will invalidate the warranty.
If the display shows the warning light
condenser has exceeded the safety limits set by the manufacturer. The reasons may be as follows:
• The space at the bottom of the unit (8 cm) was blocked, preventing the air exchange.
• The ambient temperature and humidity are too high.
• The condenser is completely blocked with dust, compromising the ventilation.
Clean it as indicated in section 4.1.
5.3 HEATED FRAME AND RAIL
An heating element is installed on all the showcases (Parete -> Frame ) (Teca -> Rail) which can be activated with the
AUX key on the thermo-regulator (excluding models with
This technical device solves the problem of condensation on the metal parts due to the difference of temperature
between the inside of the showcase and the ambient temperature, especially in places with very high temperature and
humidity.
It is very important to use this feature in tropical countries and marine locations because even a small presence of
condense for long periods may damage the external decorative coating of the showcase.
In locations with continental climate with normal temperature and humidity conditions it is not necessary to use this
device. The same goes for the showcase set at the storage temperature (+14 +16 °C).
5.4 CENTRAL COOLING SYSTEM
2
1
5
inside air flow
ambien air suction
warm air outlet
The cooling serpentine
and the internal fans
1
compressor
, the horizontal condensing unit with the fan with pressing blade
3
condensation water
are placed in a special lowered tank. With this solution, although installing a standard compressor, the
5
height of the base is limited (150 mm) since it is used the lower space where feet are located (80 mm). The circulation of the
condensation air is blown through the front bottom part.
MINIMUM ADJUSTABLE TEMPERATURE
CONDENSER TEMPERATURE ALARM
it shows that the temperature detected by the second probe placed on the
)
4
3
are located in the middle of the cabinet between the aluminium panels. The
2
15
STANDARD
OPTIONAL
OPT-EAP
Rear air expulsion
OPTIONAL
OPT-PUR
Unit set for remote
compressor connection
and the basin for the evaporation of the
4
≥ 90 mm