Tilslutninger
Nødvendige tilslutninger
Klemme:
25-26 Forsyningsspænding 24 V a.c.
20-21 Pt 1000 føler ved gaskølerafgang (S GC 2 )
14-15 Tryktransmitter type MBS 3000, 0-160 bar, 060G1112
For at registrere det korrekte tryk skal den monteres så
tæt ved gaskøleren som muligt.
2-5
Strømudgang til styring af ICMT ventil.
Applicationbestemte tilslutninger
Klemme:
1-2
Kontaktfunktion til start/stop af reguleringen.
Åben forbindelse giver regulering. Sluttet vil stoppe
reguleringen
12-13 Alarmrelæet
Der er forbindelse imellem 12 og 13 i alarmsituationer.
18-19 Optional. Der kan tilsluttes en tryktransmitter, så trykket
i receiveren kan følges. Tryktransmitteren skal være en
MBS 3000, 0-100 bar, 060G1107. Tilslutningen vil kræve en
ekstern strømforsyning til tryktransmitteren.
3-4
Datakommunikation
Monteres kun, hvis der også er monteret et datakommuni-
kationsmodul.
Det er vigtigt, at installationen af datakommunikations-
kablet udføres korrekt.
Se separat litteratur nr. RC8AC...
2
4 mA =
20 mA = ventil åben
DANSK
Instructions RI8MD352 © Danfoss 4/2008
ventil lukket,
Valve closed,
Valve open
Connections
Necessary connections
Terminals:
25-26 Supply voltage 24 V a.c.
20-21 Pt 1000 sensor at gas cooler outlet (S GC 2 )
14-15 Pressure transmitter type MBS 3000, 0-160 bar, 060G1112
To register the correct pressure it must be mounted as
close as possible to the gas cooler.
2-5
Power output to control the ICMT valve.
Application dependent connections
Terminals:
1-2
Switch function to start/stop regulation.
Open connection produces regulation. Closed will stop
regulation.
12-13 Alarm relay
There is connection between 12 and 13 in alarm situa tions
18-19 Optional. A pressure transmitter can be connected so
that the pressure in the receiver can be monitored. The
pressure transmitter must be an MBS 3000, 0-100 bar,
060G1107. The connection will require an external power
supply to the pressure transmitter.
3-4
Data communication
Mount only, if a data communication module has been
mounted.
It is important that the installation of the data communi-
cation cable be done correctly. Cf. separate literature No.
RC8AC...