Sommaire des Matières pour SUPREME FEM10-M2401AM-A
Page 1
Modèles : (3 CONDUCTEURS 120/240 – 60 – 1) MULTI - POSITION FEM10-M2401AM-A FEM15-M2401AM-A FEM18-M2401AM-A FEM20-M2401AM-A FEM23-M2401AM-A FEM20-M2401BM-A FEM23-M2401BM-A FEM27-M2401BM-A Attention : Ne pas altérer votre INSTALLATEUR / TECHNICIEN : unité ou ses contrôles. Appeler un technicien qualifié. UTILISER RENSEIGNEMENTS...
Page 2
TABLE DES MATIÈRES 1 RÈGLES DE SÉCURITÉ....................3 1.1 SIGNALISATION DANGER, MISE EN GARDE ET AVERTISSEMENT..........3 1.2 REMARQUES IMPORTANTES......................3 1.3 RISQUE DE GEL..........................3 2 INSTALLATION ......................3 2.1 EMPLACEMENT ..........................4 2.2 DÉGAGEMENT DES MATÉRIAUX COMBUSTIBLES ................. 4 2.3 CONFIGURATIONS ..........................
Page 3
1 RÈGLES DE SÉCURITÉ MISE EN GARDE SIGNALISATION DANGER, MISE L’installation ou les réparations par du personnel non GARDE ET AVERTISSEMENT qualifié peuvent entraîner des risques pour vous et à autrui. L’installation DOIT être conforme aux codes locaux ou, dans Comprenez bien la portée des mots suivants : DANGER, MISE le cas d’absence de codes locaux, elle doit être conforme EN GARDE ou AVERTISSEMENT.
Page 4
pratiquée dans le côté de l’unité. Se référer à la figure 1 pour EMPLACEMENT plus de détails. MISE EN GARDE Figure 1 Risque d’incendie ou d'explosion. L’appareil doit être installé au niveau. Ne jamais installer avec une inclinaison vers l’avant. Ne pas ranger ou utiliser d'essence ou toutes autres substances inflammables à...
Page 5
Figure 3 Thermostat 1-stage, chauffage électrique seulement RACCORDEMENT ÉLECTRIQUE Thermostat 2-stage, chauffage électrique seulement La fournaise est totalement pré-câblée et tout câblage sur chantier doit être raccordé aux blocs à bornes fournis. En outre, la fournaise SUPRÊME requiert une alimentation avec 3 fils de service de 120/240 volts.
Page 6
d’air en fonction de la pression statique dans la section 2.5.1. Ajustement de l’anticipateur (si requis) sur un « Spécifications techniques », p.10 de ce manuel. thermostat équipé d’un ajustement d’anticipateur Pour l’ajustement du débit d’air en mode chauffage, le fil orange de chaleur.
Page 7
2.7.1. SÉQUENCE DE FONCTIONNEMENT Humidificateur et filtre électronique Cet appareil est équipé d’un bornier 120 Vac pour raccordement En mode chauffage d’accessoires pour maximum ampères. Le thermostat ferme le circuit R-W1, activant ainsi les humidificateur ainsi qu’un filtre électronique peuvent donc être séquenceurs et les éléments du premier étage de raccordés aux bornes «...
Page 8
Le disjoncteur est installé pour protéger les conducteurs du 3.4.2. Vérification des limiteurs de température circuit du moteur et des contrôles. Si l’unité ne fonctionne pas, Après que l’appareil de chauffage central ait fonctionné durant pousser sur le bouton du disjoncteur pour vérifier si celui-ci n’a au mois 15 minutes, restreindre l’entrée d’air en bloquant les pas réagi à...
Page 9
5 INFORMATION Modèle : Numéro de série : Date d’installation de la fournaise : Nos. tél. service – Jour : Soir : Nom et adresse du technicien de service : RÉSULTAT DE MISE EN MARCHE Voltage : Courant total consommé par les éléments : Température de l’air chaud d’alimentation : Température de l’air de retour : Pression statique dans le conduit d’alimentation en air :...
Page 10
TABLEAU 1 Spécifications techniques FEMxx -M2401AM-A FEMxx -M2401BM-A TAUX ET PERFORMANCE Puissance (Kw) (xx ) Capacité net (BTU/h) 34120 51180 61420 68240 78480 68240 78480 92130 Plage de la hausse de temp. de chauffage (F) 40-50 45-60 50-75 55-75 60-80 55-75 60-80 60-80...
Page 11
TABLEAU 2 Débit d’air (PCM) – SUPRÊME avec un moteur de 1/3 HP Vitesse du Pression statique (en pouce de C.E.) ventilateur MED-LOW MED-HIGH 1090 1050 1010 HIGH 1285 1250 1220 1185 1150 1120 1085 Les valeurs de débit d'air sont en pied cube par minute (PCM) arrondis à 5 PCM le plus près Données prisent avec le filtre à...
Page 18
LISTE DE PIÈCES Vue explosée Se référer au tableau 4, p.20 B50002F...
Page 19
LISTE DE PIÈCES SUPRÊME avec moteur 1/3 HP et 1 HP : FEMxx-M2401 M-A et FEMxx-M2401 ITEM No DESSIN DESCRIPTION COMMENTAIRES B03274-01 ASS PLAQUE ELEMENT FEM-10KW (1/3 HP) Comprend item 11 B03275-01 ASS PLAQUE ELEMENT FEM-15KW (1/3 HP) Comprend item 11 B03276-01 ASS PLAQUE ELEMENT FEM-18KW (1/3 HP) Comprend item 11...
Page 20
TABLEAU 4 (Se référer à la Liste de Pièces, item 18, page 19) *No de FEM10 FEM15 FEM18/20 FEM23 FEM27 Item séquenceur Modèle No. ICP Modèle No. ICP Modèle No. ICP Modèle No. ICP Modèle No. ICP 18 A 305563 R02N018 305563 R02N018...
Page 21
(3 WIRES 120/240 – 60 – 1) Models: MULTI POSITION FEM10-M2401AM-A FEM15-M2401AM-A FEM18-M2401AM-A FEM20-M2401AM-A FEM23-M2401AM-A FEM20-M2401BM-A FEM23-M2401BM-A FEM27-M2401BM-A Caution: Do not tamper with INSTALLER / SERVICE TECHNICIAN: the unit or its controls. Call a qualified service technician. USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND...
Page 22
FIGURE 4 - MANUAL FURNACE CONTROLS ....................8 TABLE 1 - TECHNICAL SPECIFICATIONS....................10 TABLE 2 - AIR FLOW (CFM) – SUPREME WITH 1/3 HP MOTOR ...............11 TABLE 3 - AIR FLOW (CFM) – SUPREME WITH 1 HP MOTOR ..............11 FIGURE 5 - DIMENSIONS..........................11 FIGURE 6 - WIRING DIAGRAM 10KW WITH 1/3 HP MOTOR ..............12...
Page 23
1 SAFETY REGULATIONS WARNING SAFETY LABELING WARNING Installation and repairs performed by unqualified persons SIGNS can result in hazards to them and to others. Installations must conform to local codes or, in the absence of same, to The words DANGER, WARNING and CAUTION are used to codes of the country having jurisdiction identify the levels of seriousness of certain hazards.
Page 24
Figure 1 POSITIONING THE FURNACE WARNING Fire and explosion hazard. The furnace must be installed in a level position, never where it will slope toward the front. Do not store or use gasoline or any other flammable substances near the furnace Non-observance of these instructions will potentially result in death, bodily injury and/or property damage.
Page 25
2-stage thermostat, electric heating only ELECTRICAL SYSTEM The SUPREME furnace is completely pre-wired and all field wiring must be connected to the terminal blocks on the unit. It requires a 120/240 volt, 3-wire power supply. WARNING Risk of fire. The conductor sizing must conform to the last edition of the local or national codes.
Page 26
LOW, MED- LOW, MED-HIGH or HIGH blower speed. Blower speeds are The SUPREME furnace is equipped with a filter frame for the adjusted in factory for 0.5 inch static pressure. blower compartment. It must be installed on the outside of one of the three sides or the bottom of the furnace.
Page 27
2.7.1. Cooling mode Humidifier and electronic air cleaner The thermostat closes the R-G circuit, thereby This unit is equipped with a 120 VAC terminal for the connection activating the 24 VAC R-1 relay. The blower starts up of accessories up to a maximum of 2 amps. A humidifier and an to cooling speed.
Page 28
AIRFLOW VERIFICATION 4 MAINTENANCE Verify the airflow by taking readings of the following points, WARNING while the elements are in the heating mode: • Total amperage of all the heating elements; Electrical shock hazard. • Voltage at the furnace; Turn OFF power to the furnace before any disassembly or •...
Page 29
5 INFORMATION Model: Serial number: Furnace installation date: Service telephone # - Day: Night: Dealer name and address: START-UP RESULTS Voltage: Total current consumed by the elements: Supply air temperature: Return air temperature: Supply air duct static pressure: Return air duct static pressure: Total pressure: Calculated air flow: Current consumed by the blower motor:...
Page 30
TABLE 1 Technical Specifications FEMxx -M2401AM-A FEMxx -M2401BM-A RATINGS AND PERFORMANCE Power (Kw) (xx ) Net capacity (BTU/h) 34120 51180 61420 68240 78480 68240 78480 92130 Heating temperature rise range (F) 40-50 45-60 50-75 55-75 60-80 55-75 60-80 60-80 ELECTRICAL SYSTEM Volts - Hertz - Phase 3 wires 120/240 - 60 - 1 Electrical element #1 (Kw)
Page 31
TABLE 2 Air Flow (CFM) – SUPREME with 1/3 HP motor Static Pressure Blower Speed MED-LOW MED-HIGH 1090 1050 1010 HIGH 1285 1250 1220 1185 1150 1120 1085 The airflow values are expressed in cubic feet per minute (CFM’), rounded to 5 CFM more or less.
Page 32
FIGURE 6 Wiring Diagram 10 kW with 1/3 HP motor...
Page 33
FIGURE 7 Wiring Diagram 15 kW with 1/3 HP motor...
Page 34
FIGURE 8 Wiring Diagram 18 and 20 kW with 1/3 HP motor and 20 kW with 1.0 HP...
Page 35
FIGURE 9 Wiring Diagram 23 kW with 1/3 HP and 1 HP motor...
Page 36
FIGURE 10 Wiring Diagram 27 kW with 1 HP motor...
Page 38
PARTS LIST Exploded View Please refer to Table 4, p.20 B50002F...
Page 39
PARTS LIST SUPREME with 1/3 HP and 1 HP motor: FEMxx-M2401 M-A and FEMxx-M2401 ITEM PART # DESCRIPTION COMMENTS B03274-01 HEATING ELEMENT PLATE ASSEMBLY FEM-10kW (1/3 HP) Item 11 included B03275-01 HEATING ELEMENT PLATE ASSEMBLY FEM-15kW (1/3 HP) Item 11 included...
Page 40
TABLE 4 (Please refer to the Parts List, item 18, page 19) Sequencer FEM10 FEM15 FEM18/20 FEM23 FEM27 Item Part # ICP # Part # ICP # Part # ICP # Part # ICP # Part # ICP # number* 305563 R02N018 305563...