IMPORTANT: Provide each unit with a single-phase AC un-switched power supply from a 120 V to 347 V circuit used for normal lighting.
PRODUCT DAMAGE WILL OCCUR IF THE RATED INPUT VOLTAGE IS EXCEEDED.
WARNING: During installation of remotes, input wires from main unit to remote units must NOT be connected to each other or connected to
ground. Failure to due so will lead to failure of the main unit.
NOTE: The battery must be connected to the charger board prior to applying AC power to the unit. Battery damage may occur if the battery is
connected longer than 24 hours without continuous AC power provided. See also "Important Battery Information", page 3.
The maximum mounting height of INDL SP640L, SP1100L, SP2200L with tilt and swivel lamp heads is 31.9 feet, 47.2 feet, 67.5
NOTE:
feet respectively, to meet the minimum illumination requirements of NFPA 101 (current Life Safety Code).
NOTE:
Before installation, choose a location that allows adequate clearance for sliding the Rear Housing onto the Mounting Bracket
(minimum 6-1/2" above top edge of Bracket)
NOTE: Do not connect battery or power unit until remote units (if applicable) are fully connected and wires are isolated from other
potentials (i.e. remote wires shall be isolated from earth ground).
MOUNTING BRACKET
Universal Mounting Bracket
1
Wall/Ceiling
Mounting
)
Holes (4
Mounting
Bayonets (4)
a. Wall/Ceiling mounting-
Install using four (4) 30 lbs. min. Pullout rated fasteners. Mounting surface should be suitable to support 120 lbs.
b. Pole/Column Mounting-
1.
Unistrut Mounting holes for most standard configurations.
Steel Banding Slots for routing around poles and I-beams. (See "Pole Mount Banding slots "above).
2.
After the Mounting Bracket is in place and the conduit is near, slide the enclosure downward onto the Mounting Bayonets
(See Figures 2). The enclosure will be in place when the snap-lock feature is engaged in the hole in the Mounting Bracket.
SURFACE CONDUIT MOUNTING
At the top left and both sides of the rear housing, create an
1
appropriate hole using a drill. Attach conduit and secure
mounting plate to wall surface using fasteners with a minimum
pullout rating of 30 lbs. each.
IMPORTANT: prior to drilling out
a hole on the top conduit
location, remove the charger
board assembly to ensure no
damage occurs to the charger
board.
Three drill location
provided for conduit entry
INSTALLATION and MOUNTING
Rear housing snap lock
feature works in this
hole
Unistrut
Holes (4)
Pole Mount Banding
Slots (8)
Locate mounting bracket in desired location using "Wall/Ceiling Mounting Holes" (see Fig. 1).
LIFE SAFETY SOLUTIONS
TEL: 800-705-SERV (7378)
techsupport-emergency@acuitybrands.com
2
Mounting
®
See Wiring Diagram, page 6. Make code-
2
approved wire connections to the AC power
supply and remote lamps (if applicable).
Conduit openings
www.lithonia.com
Part # 912-00031-001
Rev. B, 5/2019