Instructions for Lithonia Lighting ECRM Models
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND
WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR SIGNIFICANT
PROPERTY DAMAGE. For your protection, read and follow these warnings
and instructions carefully before installing or maintaining this equipment.
These instructions do not attempt to cover all installation and maintenance
situations. If you do not understand these instructions or additional
information is required, contact Lithonia Lighting or your local Lithonia
Lighting distributor.
WARNING: RISK OF ELECTRIC SHOCK - NEVER CONNECT TO,
DISCONNECT FROM, OR SERVICE WHILE EQUIPMENT IS ENERGIZED.
WARNING: RISK OF FIRE. Lamps are hot. Keep combustible
material away from hot parts. Observe lamp manufacture's warnings,
recommendations and restrictions on lamp operation and maintenance. Make sure lamps are correctly installed.
CAUTION: The battery in this unit may not be fully charged. After continuous AC power is connected to unit, let battery charge for at
least 24 hours, then normal operation of this unit should take effect. To check, press the TEST button. The lamps on the unit should
turn on.
IMPORTANT SAFEGUARDS: When using electrical equipment, basic safety precautions should always be followed, including the following:
Do not use outdoors. Damp location only.
•
•
Consult local building code for approved wiring and installation.
•
Disconnect AC power before servicing and installation.
•
Do not mount near gas or electric heaters.
•
Do not use this equipment for anything other than its intended use.
•
The use of accessory equipment not recommended by the manufacturer will void product listing and warranty and may cause an unsafe condition.
•
Any service on this equipment should be performed by
•
Equipment should be mounted in locations and at heights where it will not be subject to tampering by unauthorized personnel.
•
Use caution when servicing batteries.
•
Cap unused wires with enclosed wire nuts or other approved method.
•
Make sure wire terminations are secure and leads are properly tucked in appropriate wire channels
NOTE: Max mounting height is 8.5 ft to achieve at least 1 ft-candle of illuminance in
emergency mode.
NOTE: This fixture will accommodate most industry standard junction box sizes (4" Square, 4"
Octagon, 3.5" Round or Octagon, or single gang junction boxes).
INSTALLATION INSTRUCTIONS (back mount):
1. Remove Running Man Legend faceplate from housing, set aside.
2. Drill or knock out appropriate knockouts on back plate to fit junction box (not included) mounting
points.
3. Drill or knock out center hole in back plate for sign supply wire leads.
4. Route sign supply wires through center hole of the back plate and make wiring connection. For
120V, use black and white wires and for 347V, use red and white wires. WARNING: Properly
insulate the unused lead with a wire nut (provided) or other approved means.
5. Secure back plate to junction box (not included).
6. Install proper Running Man Legend required in faceplate.
7. Connect battery only after continuous AC power can be provided to the unit.
8. Secure faceplate to housing.
9. Apply continuous AC power and press "TEST" button to check operation.(See OPERATION
for testing procedures)